| Date |
Text |
| 2021-02-19 17:02:29 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21020172 |
| | ADD: 416 CLEMATIS ST. |
| | CONT: STUART M LEDIS LLC |
| | TEL: 561-718-7162 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 19TH/2021 |
| | ACTION: DENIED |
| | |
| | 1) THE TITLE SHEET T-1: |
| | 1A) GENERAL NOTE # 1 INDICATES THE GOVERNING CODES |
| | ASCE-7-10. PLEASE UPDATE THE REFERENCE TO THE 2020 |
| | FBC-B CHAPTER 35 ASCE-7-16. |
| | |
| | 1B) UNDER THE HEADING OCCUPANCY SUMMARY THE DESIGNER OF |
| | RECORD LIST THE TENANT SPACE AS BUSINESS OCCUPANCY 1430 |
| | SQ. FT. USING A OCCUPANT LOAD FACTOR OF 100 S. F. |
| | GROSS. PLEASE REVIEW THE 2020 FBC-B TABLE 1004.1.2 FOR |
| | CHANGE IN THE OCCUPANT LOAD FACTOR IS NOW 150 S. F. |
| | GROSS. 1430 / 150= 9.53 OR 10 OCCUPANTS, YOU ALWAYS |
| | ROUND UP TO THE NEXT WHO OCCUPANT. |
| | |
| | 2) SHEET A-1 THE FLOOR PLAN: |
| | 2A) DESIGN CRITERIA (WIND). PLEASE NOTE THE PLAN |
| | REFERENCES THE 2017 6TH EDITION OF THE FBC-B AND ASCE |
| | 7-10. DEC. 31/ 2020 THE 7TH EDITION OF THE 2020 FBC-B |
| | WAS ADOPTED STATEWIDE AND THE ASCE 7-16, PLEASE UPDATE |
| | TO THE CURRENT CODES. |
| | |
| | 2B) DESIGN CRITERIA (WIND). LIST THE MEAN ROOF HEIGHT |
| | OF THIIS BUILDING AT 14 FEET 7 INCHES. THIS IS A FULL 2 |
| | STORY BUILDING. WITH ATTIC SPACE ON THE 2ND FLOOR |
| | BETWEEN THE CEILING JOIST AND ROOF RAFTERS. PLEASE |
| | UPDATE PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. PLANS ALSO STATE THE STRUCTURE IS PARTIAL |
| | OPEN, PLEASE EXPLAIN? |
| | |
| | 2C) THE SHEET ALSO LIST ON SHEET A-1 LIVE LOADS OF 30 |
| | PSF AND DEAD LOADS OF 25 PSF, THERE IS NO LISTING AS TO |
| | FLOOR LOADS, STAIRS, ROOF LOADS ETC. PLEASE REVIEW |
| | TABLE 1607.1 MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS. |
| | |
| | 2D) THE PLAN DOES NOT CLEARLY SHOW HOW EGRESS IS TO BE |
| | OBTAINED TO THE 2ND FLOOR WITHOUT GOING THROUGH ANOTHER |
| | TENANT SPACE. PLEASE ALSO SHOW THE ELEVATOR CLEARLY FOR |
| | THE REQUIRED VERTICAL ACCESSIBILITY. 2020 FBC-B SECTION |
| | 1016.2 EGRESS THROUGH INTERVENING SPACES. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 201.1.1. VERTICAL |
| | ACCESSIBILITY. |
| | |
| | 2E) THE UPPER HALF OF THE FLOOR PLAN THERE IS A VACANT |
| | SPACE, THERE IS NO INFORMATION AS IF THIS SPACE IS PART |
| | OF THIS PERMIT AND IF IT IS WHAT WORK IS TO OCCUR IN |
| | THIS SPACE. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. THE PROPOSED PLAN IT WOULD APPEAR ON THE 1ST |
| | FLOOR BUT THERE IS NO TENANT ADDRESS AS TO TENANT |
| | SPACE. 2020 FLORIDA BUILDING CODE W 2020 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2F) THE TITLEBLOCK INDICATES WORK FOR THIS PERMIT IS |
| | FOR A VETERINARY OFFICE. THE PERMIT APPLICATION STATES |
| | UNDER THE DESCRIPTION OF WORK INTERIOR RENOVATION, |
| | PHARMACY & VETERINARY OFFICE. THE PLANS DO NOT SHOW |
| | WORK TO BE COMPLETED FOR A PHARMACY. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |