Plan Review Notes
Plan Review Notes For Permit 21020169
Permit Number 21020169
Review Stop P
Sequence Number 1
Notes
Date Text
2021-02-12 11:11:301ST REVIEW FBC-2017 PLUMBING
 REVISION- 21020169
 MASTER PERMIT- 20120299
 2/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT REVISED TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW. THE PUMP'S
 MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED
 TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE
 PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE
 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER
 MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW
 RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF
 THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE
 TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM
 COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, HEAT PUMP, FILTER, AND CHLORINATOR.
 ALL SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 2) PLEASE SUBMIT THE REVISED POOL PUMP CURVE. IDENTIFY
 THE PUMP CURVE, WHICH CURVE KEY IS SPECIFIC TO THE PUMP
 BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM
 THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER
 THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved