Plan Review Notes
Plan Review Notes For Permit 21020152
Permit Number 21020152
Review Stop E
Sequence Number 1
Notes
Date Text
2021-02-18 11:41:24CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) NEW DISCONNECT SWITCH 2P/30 A IS NOW CONNECTED TO
 SUPPLY SIDE OF SERVICE WHICH MAKES IT A SECOND SERVICE
 DISCONNECTING MEANS AND IT SHOULD HAVE A RATING OF NOT
 LESS THAN 60 AMPS. AMPACITY OF CONDUCTOR SHOULD ALSO BE
 RATED FOR 60 AMPS. NEC 230.79(D)
 2) PLEASE SPECIFY INTERRUPTING CAPACITY OF NEW
 DISCONNECTING MEANS (IT SHOULD BE AT LEAST SAME AS THE
 NEW PV PANEL)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  