| 2021-02-19 09:38:17 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | IT SEEMS THERE ARE SOME INCONSISTENCIES BETWEEN RISER |
| | DIAGRAM AND PANEL SCHEDULES THAT NEED CLARIFICATION OR |
| | CORRECTIONS |
| | |
| | 1) RAYCAP BREAKER PANEL SCHEDULE SHOWS ONE 60 AMPS MAIN |
| | BREAKER BUT POWER PANEL BREAKER SCHEDULE SHOWS TWO 30 |
| | AMPS BREAKERS FOR RAYCAP FEEDERS. PLEASE CLARIFY AND |
| | CORRECT AS NEEDED. |
| | 2) RISER DIAGRAM SHOWS ONE RAYCAP PANEL, BUT POWER |
| | PANEL BREAKER SCHEDULE SHOWS TWO 30 AMPS RAYCAP |
| | FEEDERS. POWER PANEL BREAKER LISTS THE TWO CIRCUITS AS |
| | ONE POLE BREAKER, BUT RISER APPEARS TO INDICATE THAT IS |
| | ONE CIRCUIT WITH A 2-POLE BREAKER. PLEASE CLARIFY AND |
| | CORRECT AS NEEDED. |
| | 3) RISER DIAGRAM, NOTE 2, SHOWS 1#3-10 SEOW CONDUCTOR |
| | FOR RAYCAP PANEL. DOES THIS MEAN 2#3 + 1#10 G OR DOES |
| | IT MEAN 2#10 + 1#10 G CONDUCTORS? PLEASE CLARIFY AND |
| | CORRECT AS NEEDED. |
| | 4) RISER DIAGRAM SHOWS THREE CIRCUITS FROM RAYCAP PANEL |
| | TO THREE POWER SUPPLIES. PLEASE INCLUDE THESE CIRCUITS |
| | IN RAYCAP PANEL SCHEDULE |
| | 5) PLEASE PROVIDE AVAILABLE FAULT CURRENT AT SERVICE |
| | EQUIPMENT AND MAIN SERVICE POWER PANEL |
| | 6) PLEASE SPECIFY AIC RATINGS FOR MAIN PANEL AND RAYCAP |
| | PANEL |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| | MS |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |