| Date |
Text |
| 2021-07-02 16:44:56 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT-21020115 |
| | 7/2/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS F1 & F2: BASED ON TELEPHONE CALL WITH THE |
| | ENGINEER OF RECORD, THE BATHROOM IS BEING DESIGNED TO |
| | MEET FULL COMPLIANCE WITH THE FBC ACC AND NOT THE FAIR |
| | HOUSING ACT DESIGN MANUAL. IF DESIGNED A AS A |
| | TRANSFER-TYPE SHOWER UNDER SECTIONS 608.2 & 608.2.1 FBC |
| | ACC THE SHOWER SHALL BE 36 INCHES BY 36 INCHES CLEAR |
| | INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF |
| | OPPOSING SIDES AND SHALL HAVE A 36 INCH-WIDE MINIMUM |
| | ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE |
| | MEANING A CLEAR FLOOR SPACE OF 36 INCHES WIDE MINIMUM |
| | BY 48 INCHES LONG MINIMUM MEASURED FROM THE CONTROL |
| | WALL SHALL BE PROVIDED. IF DESIGNED AS A STANDARD |
| | ROLL-IN TYPE SHOWER COMPARTMENT UNDER SECTION 608.2.2, |
| | IT SHALL BE 30 INCHES WIDE MINIMUM BY 60 INCHES DEEP |
| | MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| | POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES |
| | (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER |
| | COMPARTMENT. |
| | |
| | THE CURRENT PLAN SHOWS A 36 IN. X 48 IN. SHOWER WHICH |
| | DOES NOT MEET FBC ACC COMPLIANCE, BUT DOES MEET |
| | COMPLIANCE WITH THE FAIR HOUSING DESIGN MANUAL |
| | SPECIFICATIONS AS INDICATED ON PAGES 7.56 AND 7.58 OF |
| | THE MANUAL. |
| | |
| | 2) F2, DETAILS B & F: PLEASE INDICATE THE CONTROL SHALL |
| | BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM |
| | THE CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. |
| | PLEASE MATCH THE LOCATION OF THE FAUCET AS SHOWN IN THE |
| | NORTH WALL DETAIL WITH DETAILS B & F, OR REMOVE THE 18" |
| | MEASUREMENT- SECTION 608.5.1 FBC ACC. |
| | |
| | 3) F2: PLEASE PROVIDE THE TOE CLEARANCES FOR THE |
| | ACCESSIBLE LAVATORY AND SINK AS SHOWN IN FIGURE 306.2 |
| | FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |