Plan Review Notes
Plan Review Notes For Permit 21020115
Permit Number 21020115
Review Stop P
Sequence Number 3
Notes
Date Text
2021-07-02 16:44:563RD REVIEW FBC-2020 PLUMBING
 PERMIT-21020115
 7/2/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS F1 & F2: BASED ON TELEPHONE CALL WITH THE
 ENGINEER OF RECORD, THE BATHROOM IS BEING DESIGNED TO
 MEET FULL COMPLIANCE WITH THE FBC ACC AND NOT THE FAIR
 HOUSING ACT DESIGN MANUAL. IF DESIGNED A AS A
 TRANSFER-TYPE SHOWER UNDER SECTIONS 608.2 & 608.2.1 FBC
 ACC THE SHOWER SHALL BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36 INCH-WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 MEANING A CLEAR FLOOR SPACE OF 36 INCHES WIDE MINIMUM
 BY 48 INCHES LONG MINIMUM MEASURED FROM THE CONTROL
 WALL SHALL BE PROVIDED. IF DESIGNED AS A STANDARD
 ROLL-IN TYPE SHOWER COMPARTMENT UNDER SECTION 608.2.2,
 IT SHALL BE 30 INCHES WIDE MINIMUM BY 60 INCHES DEEP
 MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
  
 THE CURRENT PLAN SHOWS A 36 IN. X 48 IN. SHOWER WHICH
 DOES NOT MEET FBC ACC COMPLIANCE, BUT DOES MEET
 COMPLIANCE WITH THE FAIR HOUSING DESIGN MANUAL
 SPECIFICATIONS AS INDICATED ON PAGES 7.56 AND 7.58 OF
 THE MANUAL.
  
 2) F2, DETAILS B & F: PLEASE INDICATE THE CONTROL SHALL
 BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM
 THE CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.
 PLEASE MATCH THE LOCATION OF THE FAUCET AS SHOWN IN THE
 NORTH WALL DETAIL WITH DETAILS B & F, OR REMOVE THE 18"
 MEASUREMENT- SECTION 608.5.1 FBC ACC.
  
 3) F2: PLEASE PROVIDE THE TOE CLEARANCES FOR THE
 ACCESSIBLE LAVATORY AND SINK AS SHOWN IN FIGURE 306.2
 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  