2021-06-08 18:08:552ND REVIEW FBC-2020 PLUMBING
 PERMIT-21020115
 6/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) SHEET F1, BATHROOM DETAILS- FBC ACC COMPLIANCES:
  
 A) FAILED- F2: PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS FOR THE WATER CLOSET, LAVATORY SINK, AND
 THE SHOWER- SECTIONS 604.3, 606.2, AND 608.2.2. THE 30
 X 48 INCH CLEAR FLOOR SPACE FOR THE SHOWER NOT
 PROVIDED. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE FOR THE LAVATORY UNLESS A 30X48 INCH CLEAR FLOOR
 SPACE IS PROVIDED BEYOND THE ARC OF THE DOOR- SECTION
 603.2.3 (2) FBC ACC.
 D) FAILED- F2: LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS
 OF GRAB BARS FOR THE WATER CLOSET- 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. IT IS ACKNOWLEDGED THAT ONLY
 THE REINFORCEMENT IS REQUIRED HOWEVER THE GRAB BARS
 SHALL BE POSITIONED 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACES- NOT TO THE CENTERS OF THE BARS.
 G) FAILED- F2: COMPLETE KNEE AND TOE CLEARANCES FOR THE
 LAVATORY- 606.2. PLEASE SEE FIGURE 306.3 AND CORRECT
 THE KNEE AND TOE CLEARANCE DRAWINGS FOR THE LAV AND
 KITCHEN SINK.THE KNEE CLEARANCE SHALL EXTEND A MINIMUM
 OF 8 INCHES BELOW THE SINK MEASURED FROM THE FRONT
 EDGE.
 H) FAILED- F2: LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS
 OF GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3
 AND 608.3.1. IT IS ACKNOWLEDGED THAT ONLY THE
 REINFORCEMENT IS REQUIRED HOWEVER THE GRAB BARS SHALL
 BE POSITIONED 33 INCHES MINIMUM AND 36 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE
 GRIPPING SURFACES- NOT TO THE CENTERS OF THE BARS.
 I) FAILED- F2: LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.1. THE CONTROL,
 FAUCET, AND SHOWER SPRAY SHALL BE LOCATED ON THE
 CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE OF
 THE SEAT TOWARD THE SHOWER OPENING.
 K) FAILED- F2: LOCATION OF ACCESSIBLE SHOWER SEAT-
 SECTIONS 610.3 & 610.3.2. THE LOCATION OF THE SEAT IS
 CORRECT HOWEVER THE ACTUAL SEAT DIMENSIONS ARE NOT
 SHOWN IN ACCORDANCE WITH FIGURE 610.3.2.
 L) FAILED- F2: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE KITCHEN SINK- SECTION 606.2. THE
 CLEAR FLOOR SPACE DIAGRAM DOES NOT APPEAR TO EXTEND
 INTO THE KNEE AND TOE SPACE- FIGURE 306.2.
  
 5) FAILED- F1: SHOW THE SOURCE OF HOT WATER AND
 INDICATE IF COLD OR TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORY SINK- SECTIONS 419.5 AND 607.1 FBC P.
 BECAUSE HOT WATER IS BEING PROVIDED IT SHALL BE
 TEMPERED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  