| 2021-06-08 18:08:55 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21020115 |
| | 6/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH ADDITIONAL NOTES. |
| | |
| | 1) SHEET F1, BATHROOM DETAILS- FBC ACC COMPLIANCES: |
| | |
| | A) FAILED- F2: PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS |
| | AND DIMENSIONS FOR THE WATER CLOSET, LAVATORY SINK, AND |
| | THE SHOWER- SECTIONS 604.3, 606.2, AND 608.2.2. THE 30 |
| | X 48 INCH CLEAR FLOOR SPACE FOR THE SHOWER NOT |
| | PROVIDED. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE FOR THE LAVATORY UNLESS A 30X48 INCH CLEAR FLOOR |
| | SPACE IS PROVIDED BEYOND THE ARC OF THE DOOR- SECTION |
| | 603.2.3 (2) FBC ACC. |
| | D) FAILED- F2: LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS |
| | OF GRAB BARS FOR THE WATER CLOSET- 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. IT IS ACKNOWLEDGED THAT ONLY |
| | THE REINFORCEMENT IS REQUIRED HOWEVER THE GRAB BARS |
| | SHALL BE POSITIONED 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACES- NOT TO THE CENTERS OF THE BARS. |
| | G) FAILED- F2: COMPLETE KNEE AND TOE CLEARANCES FOR THE |
| | LAVATORY- 606.2. PLEASE SEE FIGURE 306.3 AND CORRECT |
| | THE KNEE AND TOE CLEARANCE DRAWINGS FOR THE LAV AND |
| | KITCHEN SINK.THE KNEE CLEARANCE SHALL EXTEND A MINIMUM |
| | OF 8 INCHES BELOW THE SINK MEASURED FROM THE FRONT |
| | EDGE. |
| | H) FAILED- F2: LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS |
| | OF GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 |
| | AND 608.3.1. IT IS ACKNOWLEDGED THAT ONLY THE |
| | REINFORCEMENT IS REQUIRED HOWEVER THE GRAB BARS SHALL |
| | BE POSITIONED 33 INCHES MINIMUM AND 36 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACES- NOT TO THE CENTERS OF THE BARS. |
| | I) FAILED- F2: LOCATION OF CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SECTION 608.5.1. THE CONTROL, |
| | FAUCET, AND SHOWER SPRAY SHALL BE LOCATED ON THE |
| | CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE OF |
| | THE SEAT TOWARD THE SHOWER OPENING. |
| | K) FAILED- F2: LOCATION OF ACCESSIBLE SHOWER SEAT- |
| | SECTIONS 610.3 & 610.3.2. THE LOCATION OF THE SEAT IS |
| | CORRECT HOWEVER THE ACTUAL SEAT DIMENSIONS ARE NOT |
| | SHOWN IN ACCORDANCE WITH FIGURE 610.3.2. |
| | L) FAILED- F2: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS FOR THE KITCHEN SINK- SECTION 606.2. THE |
| | CLEAR FLOOR SPACE DIAGRAM DOES NOT APPEAR TO EXTEND |
| | INTO THE KNEE AND TOE SPACE- FIGURE 306.2. |
| | |
| | 5) FAILED- F1: SHOW THE SOURCE OF HOT WATER AND |
| | INDICATE IF COLD OR TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORY SINK- SECTIONS 419.5 AND 607.1 FBC P. |
| | BECAUSE HOT WATER IS BEING PROVIDED IT SHALL BE |
| | TEMPERED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |