Plan Review Notes
Plan Review Notes For Permit 21020115
Permit Number 21020115
Review Stop P
Sequence Number 1
Notes
Date Text
2021-02-22 09:41:541ST REVIEW FBC-2020 PLUMBING
 PERMIT-21020115
 2/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COVER SHEET: PLEASE UPDATE THE CODE REFERENCES- THE
 FBC- 2020 7TH EDITION CODES WENT INTO EFFECT ON
 12/31/20.
  
 2) COVER SHEET: PROVIDE THE OCCUPANCY CLASSIFICATION OF
 THE SPACE AND PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 PLUMBING FIXTURES.
  
 3) COVER SHEET: PLEASE CLARIFY THE SCOPE OF WORK. THE
 FBC ACC IS THE GOVERNING ACCESSIBILITY CODE. REFER TO
 SECTION 101.1.2- ALL NEW OR ALTERED PUBLIC BUILDINGS
 AND FACILITIES, PRIVATE BUILDINGS AND FACILITIES,
 PLACES OF PUBLIC ACCOMMODATION, AND COMMERCIAL
 FACILITIES SUBJECT TO THIS CODE SHALL COMPLY WITH THIS
 CODE. PLEASE MAKE CORRECTIONS TO THE DRAWINGS PER THE
 FBC ACC SECTIONS LISTED BELOW.
  
 SHEET F1, BATHROOM DETAILS- FBC ACC COMPLIANCES:
 A) PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE WATER CLOSET, LAVATORY SINK, AND THE
 SHOWER- SECTIONS 604.3, 606.2, AND 608.2.2.
 B) PROVIDE THE HEIGHT OF THE TOILET SEAT MEASURED FROM
 THE FINISHED FLOOR- 604.4.
 C) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- 603.3
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSET- 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
 E) LOCATION OF THE WATER CLOSET FLUSH CONTROL- 604.6.
 F) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- 604.7.
 G) COMPLETE KNEE AND TOE CLEARANCES FOR THE LAVATORY-
 606.2.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1
 I) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1.
 J) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 K) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 &
 610.3.2.
 L) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS
 FOR THE KITCHEN SINK- SECTION 606.2.
  
 4) F1: PROVIDE A WATER RISER DRAWING- SECTION
 107.3.5.1.3 WPB.
  
 5) F1: SHOW THE SOURCE OF HOT WATER AND INDICATE IF
 COLD OR TEMPERED WATER WILL BE PROVIDED TO THE LAVATORY
 SINK- SECTIONS 419.5 AND 607.1 FBC P.
  
 6) F1: PROVIDE A SHOWER PAN DETAIL- SECTIONS 421.4.1-
 421.5.2 FBC P.
  
 7) PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTIONS 404,
 405, 409, 412, 419, 420, & 422- FBC P.
  
 8) F1: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  