| 2021-02-22 09:41:54 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21020115 |
| | 2/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COVER SHEET: PLEASE UPDATE THE CODE REFERENCES- THE |
| | FBC- 2020 7TH EDITION CODES WENT INTO EFFECT ON |
| | 12/31/20. |
| | |
| | 2) COVER SHEET: PROVIDE THE OCCUPANCY CLASSIFICATION OF |
| | THE SPACE AND PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF |
| | PLUMBING FIXTURES. |
| | |
| | 3) COVER SHEET: PLEASE CLARIFY THE SCOPE OF WORK. THE |
| | FBC ACC IS THE GOVERNING ACCESSIBILITY CODE. REFER TO |
| | SECTION 101.1.2- ALL NEW OR ALTERED PUBLIC BUILDINGS |
| | AND FACILITIES, PRIVATE BUILDINGS AND FACILITIES, |
| | PLACES OF PUBLIC ACCOMMODATION, AND COMMERCIAL |
| | FACILITIES SUBJECT TO THIS CODE SHALL COMPLY WITH THIS |
| | CODE. PLEASE MAKE CORRECTIONS TO THE DRAWINGS PER THE |
| | FBC ACC SECTIONS LISTED BELOW. |
| | |
| | SHEET F1, BATHROOM DETAILS- FBC ACC COMPLIANCES: |
| | A) PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND |
| | DIMENSIONS FOR THE WATER CLOSET, LAVATORY SINK, AND THE |
| | SHOWER- SECTIONS 604.3, 606.2, AND 608.2.2. |
| | B) PROVIDE THE HEIGHT OF THE TOILET SEAT MEASURED FROM |
| | THE FINISHED FLOOR- 604.4. |
| | C) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- 603.3 |
| | D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSET- 604.5 & 609.4, FIGURES |
| | 604.5.1 & 604.5.2. |
| | E) LOCATION OF THE WATER CLOSET FLUSH CONTROL- 604.6. |
| | F) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONT OF THE WATER CLOSET- 604.7. |
| | G) COMPLETE KNEE AND TOE CLEARANCES FOR THE LAVATORY- |
| | 606.2. |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.1 |
| | I) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1. |
| | J) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| | K) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 & |
| | 610.3.2. |
| | L) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| | FOR THE KITCHEN SINK- SECTION 606.2. |
| | |
| | 4) F1: PROVIDE A WATER RISER DRAWING- SECTION |
| | 107.3.5.1.3 WPB. |
| | |
| | 5) F1: SHOW THE SOURCE OF HOT WATER AND INDICATE IF |
| | COLD OR TEMPERED WATER WILL BE PROVIDED TO THE LAVATORY |
| | SINK- SECTIONS 419.5 AND 607.1 FBC P. |
| | |
| | 6) F1: PROVIDE A SHOWER PAN DETAIL- SECTIONS 421.4.1- |
| | 421.5.2 FBC P. |
| | |
| | 7) PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTIONS 404, |
| | 405, 409, 412, 419, 420, & 422- FBC P. |
| | |
| | 8) F1: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |