| 2021-02-12 12:15:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO SLOPE INDICATED FOR THE DORRWAY RAMP. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.5.3 DIMENSIONAL CRITERIA. THE FOLLOWING DIMENSIONAL |
| | CRITERIA SHALL |
| | APPLY TO RAMPS: |
| | (1) NEW RAMPS SHALL BE IN ACCORDANCE WITH TABLE |
| | 7.2.5.3(A), UNLESS |
| | OTHERWISE PERMITTED BY THE FOLLOWING: |
| | (A) TABLE 7.2.5.3(A) SHALL NOT APPLY TO INDUSTRIAL |
| | EQUIPMENT ACCESS |
| | AREAS AS PROVIDED IN 40.2.5.3. |
| | |
| | 1 IN 12 |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 2) THERE IS NO RAMP MATERIAL TYPE INDICATED. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.5.4.1 CONSTRUCTION. RAMP CONSTRUCTION SHALL BE AS |
| | FOLLOWS: |
| | (1) ALL RAMPS SERVING AS REQUIRED MEANS OF EGRESS SHALL |
| | BE OF PERMANENT |
| | FIXED CONSTRUCTION. |
| | (2) EACH RAMP IN BUILDINGS REQUIRED BY THIS CODE TO BE |
| | OF TYPE I OR |
| | TYPE II CONSTRUCTION SHALL BE ANY COMBINATION OF |
| | NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE MATERIAL OR |
| | FIRE-RETARDANT?TREATED WOOD. |
| | (3) RAMPS CONSTRUCTED WITH FIRE-RETARDANT?TREATED WOOD |
| | SHALL BE NOT |
| | MORE THA |
| | |
| | N 30 IN. (760 MM) HIGH, SHALL HAVE AN AREA OF NOT MORE |
| | THAN 3000 FT2 (277 M2), AND SHALL NOT OCCUPY MORE THAN |
| | 50 PERCENT |
| | OF THE ROOM AREA. |
| | (4) THE RAMP FLOOR AND LANDINGS SHALL BE SOLID AND |
| | WITHOUT |
| | PERFORATIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | 3) THERE IS AN INDICATION OF THE NEW BATHROOM DOOR |
| | OPENING INTO THE CORRIDOR RESTRICTING THE MEANS OF |
| | EGRESS FROM THE TWO BEDROOMS. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL |
| | LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| | AN AISLE, A CORRIDOR, |
| | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF |
| | THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | |
| | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL |
| | NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR |
| | LEAF IS EQUIPPED |
| | WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT |
| | REQUIRED BY THE PROVISIONS |
| | OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE DIMENSIONS IN |
| | COMPLIANCE |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |