Plan Review Notes
Plan Review Notes For Permit 21020115
Permit Number 21020115
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-02-12 12:15:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO SLOPE INDICATED FOR THE DORRWAY RAMP.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.5.3 DIMENSIONAL CRITERIA. THE FOLLOWING DIMENSIONAL
 CRITERIA SHALL
 APPLY TO RAMPS:
 (1) NEW RAMPS SHALL BE IN ACCORDANCE WITH TABLE
 7.2.5.3(A), UNLESS
 OTHERWISE PERMITTED BY THE FOLLOWING:
 (A) TABLE 7.2.5.3(A) SHALL NOT APPLY TO INDUSTRIAL
 EQUIPMENT ACCESS
 AREAS AS PROVIDED IN 40.2.5.3.
  
 1 IN 12
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) THERE IS NO RAMP MATERIAL TYPE INDICATED.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.5.4.1 CONSTRUCTION. RAMP CONSTRUCTION SHALL BE AS
 FOLLOWS:
 (1) ALL RAMPS SERVING AS REQUIRED MEANS OF EGRESS SHALL
 BE OF PERMANENT
 FIXED CONSTRUCTION.
 (2) EACH RAMP IN BUILDINGS REQUIRED BY THIS CODE TO BE
 OF TYPE I OR
 TYPE II CONSTRUCTION SHALL BE ANY COMBINATION OF
 NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE MATERIAL OR
 FIRE-RETARDANT?TREATED WOOD.
 (3) RAMPS CONSTRUCTED WITH FIRE-RETARDANT?TREATED WOOD
 SHALL BE NOT
 MORE THA
  
 N 30 IN. (760 MM) HIGH, SHALL HAVE AN AREA OF NOT MORE
 THAN 3000 FT2 (277 M2), AND SHALL NOT OCCUPY MORE THAN
 50 PERCENT
 OF THE ROOM AREA.
 (4) THE RAMP FLOOR AND LANDINGS SHALL BE SOLID AND
 WITHOUT
 PERFORATIONS.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
 3) THERE IS AN INDICATION OF THE NEW BATHROOM DOOR
 OPENING INTO THE CORRIDOR RESTRICTING THE MEANS OF
 EGRESS FROM THE TWO BEDROOMS.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
  
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DIMENSIONS IN
 COMPLIANCE
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  