| 2021-02-18 10:14:31 | 2ND REVIEW FBC-2020 RES. FUEL GAS. |
| | PERMIT- 21020074 |
| | 2/18/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE RESUBMITTED GAS PLANS SHALL BEAR THE ELECTRONIC |
| | SIGNATURE AND SEAL OF THE ENGINEER OF RECORD- FL. |
| | STATUTE 471.025 AND SECTION 61G15-23.005 FAC. |
| | |
| | 2) THE RESUBMITTED SIGNED AND SEALED GAS RISER SHALL |
| | SHOW THE TYPE OF PIPE, PIPE SIZE, AND LENGTH OF PIPE |
| | FROM THE PE CONNECTION TO THE POOL HEATER- SECTIONS |
| | G2413.3 & G2413.4.1 FBC RES. |
| | |
| | 3) THE RESUBMITTED PLANS AND RISER DRAWING DO NOT MATCH |
| | THE APPROVED PLANS FOR THE GAS SYSTEM UNDER PERMIT |
| | 20041097. THE APPROVED RISER DRAWING WAS REDLINED PER |
| | THE ENGINEER'S INSTRUCTIONS TO SHOW CORRECT PIPE SIZES, |
| | PIPE SIZING TABLES, AND GAS LOADS. THERE ARE NUMEROUS |
| | DEFICIENT EHD SIZES FOR THE CSST PIPING. AND INCORRECT |
| | PIPE SIZING TABLES. PLEASE SUBMIT THE CORRECT SIGNED |
| | AND SEALED GAS RISER DRAWING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |