| Plan Review Notes For Permit 21020074 |
| Permit Number |
21020074 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-02-09 17:02:35 | 1ST REVIEW FBC-2020 RES. FUEL GAS. | | | PERMIT- 21020074 | | | 2/9/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN ORDER TO ENSURE A SAFE OPERATING SYSTEM PLEASE | | | PROVIDE A COMPLETE RISER DRAWING THAT INCLUDES ALL THE | | | GAS PIPING THAT WAS INSTALLED UNDER PERMIT- 20041097 | | | FOR THE NEW HOUSE APPLIANCES AND EQUIPMENT- SECTION | | | G2412.4 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|