2021-10-18 07:06:51PLEASE PROVIDE THE SPECIFICATIONS FOR THE WALKIN
 COOLER/FREEZER. FBC 107.2.1
 ENGINEER TO PROVIDE THE REQUIREMENTS LISTED BELOW:FBC M
 1102
  
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
  
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  