| 2021-03-29 08:21:15 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21020013 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW THAT THE MAKE-UP AIR IS APPROXIMATELY |
| | EQUAL TO THE AMOUNT OF EXHAUST AIR FOR ALL EXHAUST |
| | SYSTEMS FOR THE BUILDING, INCLUDING THE BATHROOM |
| | EXHAUST FAN. FBC M 508.1 |
| | |
| | 2) PLEASE PROVIDE AN AIR BALANCE REPORT ACCORDING TO |
| | FBC 508.1.2 |
| | |
| | 3) THE 1ST REVIEW COMMENTS ADDRESSED THE FIRE WRAP FOR |
| | THE GREASE DUCT TO PROVIDE 0 CLEARANCE TO COMBUSTIBLES. |
| | PLEASE ADD A NOTE ON THE PLANS SPECIFYING THE GREASE |
| | DUCT WRAP. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |