| Date |
Text |
| 2021-04-09 10:03:10 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) SYSTEM TYPE (E2) - ROOFING SYSTEM TO BE USED ON THE |
| | PROVIDED PRODUCT APPROVAL (20-0131.01) REQUIRES |
| | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN |
| | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH |
| | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE |
| | PRODUCT APPROVAL (-52) - SEE GENERAL LIMITATION NOTE |
| | NUMBER 7 ON THE PRODUCT APPROVAL. SEE ROOF CLADDING |
| | PRESSURES ON DRAWING S-100 |
| | 2) PRODUCT APPROVAL FOR THE ROOFING SHINGLES NEEDS TO |
| | BE THE UPDATED VERSION (FL10674-R16) YOU PROVIDED (FL |
| | 10674-R8) |
| | 3) YOU CANNOT RELOCATE A DOOR OR WINDOW WITHOUT AN |
| | UPDATED PRODUCT APPROVAL FBC EXISTING BUILDING 707.4 |
| | REPLACEMENT OF WINDOWS AND DOORS. |
| | THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS, |
| | SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL |
| | BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | YOU CAN HAVE A DESIGNED CUSTOM DOOR THAT MEETS THE |
| | REQUIRED WIND LOADS - FBC R609.2.1 CUSTOM DOORS. |
| | CUSTOM (ONE-OF-A-KIND) EXTERIOR DOOR ASSEMBLIES SHALL |
| | BE TESTED BY AN APPROVED TESTING LABORATORY OR BE |
| | DESIGNED AND ENGINEERED IN ACCORDANCE WITH ACCEPTED |
| | ENGINEERING PRACTICES BY A FLORIDA REGISTERED DESIGN |
| | PROFESSIONAL. SIGNED AND SEALED COPIES OF THE RATIONAL |
| | ANALYSIS AND CALCULATIONS SHALL BE PROVIDED TO THE |
| | BUILDING OFFICIAL UPON PERMIT APPLICATION. - (WOULD |
| | NEED SIGNED AND SEALED ATTACHMENT DETAILS FROM THE |
| | ARCHITECT OR ENGINEER). |
| | |
| | A SHUTTER WOULD BE REQUIRED TO PROTECT THE GLAZING OF A |
| | CUSTOM DESIGNED DOOR - FBC R301.2.1.2 PROTECTION OF |
| | OPENINGS. |
| | EXTERIOR GLAZED OPENINGS IN BUILDINGS LOCATED IN |
| | WINDBORNE DEBRIS REGIONS SHALL BE PROTECTED FROM |
| | WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR |
| | WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST OF ASTM E1996 AND ASTM E1886 AS |
| | MODIFIED IN SECTION 301.2.1.2.1, TAS 201, 202 AND 203, |
| | OR AAMA 506, AS APPLICABLE. ( COMPLETE MIAMI DADE OR |
| | FLORIDA STATE PRODUCT APPROVAL WOULD BE REQUIRED) |