| Date |
Text |
| 2021-02-23 10:31:42 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21011181 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE MECHANICAL SYSTEMS EQUIPMENT |
| | SIZING CALCULATIONS. FBC RES M1401.3 |
| | |
| | 2) SHEET M-102: THE SECOND FLOOR AHU IS NOT IDENTIFIED, |
| | PLEASE IDENTIFY THIS UNIT. |
| | |
| | 3) PLEASE SHOW CONDENSATE DRAIN PIPING AND THE DISPOSAL |
| | LOCATION. FBC RES M1411.3 |
| | |
| | 4) WITH A GARAGE DOOR FOR STORAGE ACCESS IS THIS AREA |
| | GOING TO BE USED AS A GARAGE? IF SO PLEASE SHOW THE |
| | DUCT SYSTEM MEETS FBC RES R302.5.2 |
| | |
| | 5) PLEASE SHOW WHERE THE SUPPLY AND RETURN AIR IS BEING |
| | SUPPLIED TO THE SECOND FLOOR OF THE GUEST HOUSE. FBC M |
| | 601.6 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |