| 2021-02-18 21:45:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. CLEARLY LABEL ROOMS SO PROPER CODES CAN BE APPLIED |
| | (BEDROOM, LIVING ROOM, FLORIDA ROOM, KITCHEN ETC). FBC |
| | 107.2.1 |
| | |
| | 2. SEPARATE PERMIT REQUIRED FOR GUEST HOUSE. REMOVE |
| | GUEST HOUSE FROM PLANS AND SUBMIT FOR A SEPARTE PERMIT. |
| | FBC 107.2.1 FBC 105.1 |
| | |
| | 3. RISER SHOWN IS INCOMPLETE AND AS IS IS NOT CODE |
| | COMPLIANT. SHOW SIZE OF MAIN SERVICE DISCONNECT. TAPS |
| | SHOWN OFF MAIN DISCONNET TO 2 SEPARATE PANELS IS NOT |
| | CODE COMPLIANT. DISCONNECT WILL BE REQUIRED FOR |
| | SEPARATE STRUCTURE WHICH IS NOT SHOWN ON RISER DIAGRAM. |
| | NEC 215, NEC 220, NEC 240 NEC 225.31&32 |
| | |
| | 4. SMOKE/CARBON ALARMS REQURIED IMMEDIATLY OUTSIDE |
| | SLEEPING AREAS PER FBC-RE 314&315 |
| | |
| | 5. SMOKE ALARMS MUST BE 3FT FROM TIPS OF FAN BLADES, |
| | A/C SUPPLY REGISTERS, AND BATHROOM DOORS. |
| | |
| | 6. SEVERAL RECEPTACLE WALL SPACING VIOLATIONS |
| | THROUGHOUT PLAN NEC 210.52 |
| | |
| | 7. NOTE ON PLAN STATES ONLY ONE GROUND ROD IS REQUIRED. |
| | RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A |
| | SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL |
| | GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN |
| | ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| | NEC 250.53(A)(2); FBC RE E3608.4 |
| | |
| | 8. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | |
| | 9. NO WIRE SIZES SHOWN FROM METER CAN TO SERVICE |
| | DISCONNECT?? FBC 107.2.1 |
| | |
| | 10. A "300AMP" METER CAN TO MY KNOWLEDGE DOES NOT |
| | EXIST. PLEASE LABEL AT 400AMP OR 320AMP CONTINUOUS |
| | METER CAN. FBC 107.2.1 |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |