| 2021-02-10 16:18:11 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21011119 |
| | 2/10/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: |
| | A) THE RISER SHALL BE DESIGNED IN COMPLIANCE WITH THE |
| | FBC- 2020 7TH EDITION FUEL GAS CODE WHICH WENT INTO |
| | EFFECT ON DEC. 31, 2020. PLEASE UPDATE THE 2017 CODE |
| | REFERENCES AND THE SUBMIT THE UPDATED PIPE SIZING |
| | TABLES SECTION 107.2.1 WPB. |
| | |
| | B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM- |
| | SECTION G2413.4.1 FBC RES. |
| | |
| | C) SHOW THE FLEX CONNECTOR AT THE GENERATOR AND SUBMIT |
| | MANUFACTURER?S SPECIFICATION- SECTIONS G2422.1- |
| | G2422.1.5. |
| | |
| | D) CORRECT THE GENERATOR LOAD TO 306,000 BTU?S BASED ON |
| | THE SUBMITTED GENERATOR SPECS- SECTION G2408.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |