| 2021-03-22 15:30:27 | PROPERTY IN HISTORIC DISTRICT. SETBACKS FOR MECHANICAL |
| | EQUIPTMENT BASED ON ACCESSORY STRUCTURE SETBACKS. |
| | |
| | PASSED PERMIT. |
| 2021-02-23 16:12:29 | ZONING PLAN REVIEW |
| | ________________________________________ |
| | |
| | DATE OF REVIEW: |
| | ________________________________________ |
| | |
| | REVIEW STATUS: FAILED |
| | ________________________________________ |
| | |
| | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN |
| | REVIEW COMMENTS: |
| | |
| | 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED |
| | SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING |
| | AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION |
| | 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE |
| | THAN 4 FEET INTO A REQUIRED SETBACK. |
| | 2. REQUIRED REAR SETBACK FOR THE SF14-C3 DISTRICT IS, |
| | PURSUANT TO ZLDR SEC 94-82, 15 FEET, OR 10 PERCENT OF |
| | THE LOT DEPTH, WHICHEVER IS LESS. THE MINIMUM REAR |
| | SETBACK FOR THE GENERATOR IS 9.43 FT. |
| | |
| | ________________________________________ |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD |
| | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL |
| | [email protected] AND REQUEST TO HAVE YOUR |
| | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG |
| | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. |
| | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU |
| | ARE FINISHED UPLOADING. |
| | ________________________________________ |
| | |
| | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: |
| | |
| | KIZZI ALEXANDRE, ASSOCIATE PLANNER |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION |
| | 401 CLEMATIS STREET - P.O. BOX 3147 |
| | WEST PALM BEACH, FLORIDA 33402 |
| | |
| | P: 561.822.1442 |
| | TTY: 800.955.8771 |
| | E: [email protected] |
| | |
| | W: WPB.ORG |
| | |