Plan Review Notes
Plan Review Notes For Permit 21011112
Permit Number 21011112
Review Stop G
Sequence Number 3
Notes
Date Text
2021-12-03 13:22:153RD REVIEW FBC-2017 RES.
 PERMIT- 21011112
 12/3/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 201
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED RISER SHOWS UNDERSIZED PIPING AND
 INACCURATE LOAD. PLEASE MAKE THESE CORRECTIONS PER
 SECTION 107.3.5.3 WPB, AND CHAPTER 24 FBC RES.
 A) INCREASE TOTAL LOAD FOR LOW PRESSURE REG A- TO
 992,000 BTU?S
 B) INCREASE TOTAL LOAD FOR LOW PRESSURE REG B- TO
 398,000 BTU?S
 C) INCREASE THE PIPE SIZES DOWNSTREAM OF REGULATORS
 BASED ON THE PIPE SIZING TABLES LISTED ON THE RISER.
 OPTION 2 WOULD BE TO RELOCATE THE LOW PRESSURE REG A SO
 IT IS SERVING ONLY THE INTERIOR APPLIANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  