| 2021-12-03 13:22:15 | 3RD REVIEW FBC-2017 RES. | | | PERMIT- 21011112 | | | 12/3/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 201 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED RISER SHOWS UNDERSIZED PIPING AND | | | INACCURATE LOAD. PLEASE MAKE THESE CORRECTIONS PER | | | SECTION 107.3.5.3 WPB, AND CHAPTER 24 FBC RES. | | | A) INCREASE TOTAL LOAD FOR LOW PRESSURE REG A- TO | | | 992,000 BTU?S | | | B) INCREASE TOTAL LOAD FOR LOW PRESSURE REG B- TO | | | 398,000 BTU?S | | | C) INCREASE THE PIPE SIZES DOWNSTREAM OF REGULATORS | | | BASED ON THE PIPE SIZING TABLES LISTED ON THE RISER. | | | OPTION 2 WOULD BE TO RELOCATE THE LOW PRESSURE REG A SO | | | IT IS SERVING ONLY THE INTERIOR APPLIANCES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|