Plan Review Notes
Plan Review Notes For Permit 21011046
Permit Number 21011046
Review Stop E
Sequence Number 1
Notes
Date Text
2021-02-11 18:16:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLAN IS NOT DIGITALLY SIGNED BY THE DESIGNER OF
 RECORD
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
 2) DISCONNECT REQUIRED BY 600.6(A)(1) NO ELECTRICAL
 LAYOUT SHOWN.
  
 3) VALUE OF THE SIGN LOW (2100) PLEASE SUBMIT A SIGNED
 CONTRACT WITH THE OWNER.