| 2021-02-08 17:17:53 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21011019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: PLEASE PROVIDE CODE COMPLIANT DRAWINGS |
| | BASED ON THE CURRENT 2020 FLORIDA BUILDING CODES. FBC |
| | 107.2.1 |
| | |
| | 2) PLEASE SHOW DEMOLITION DRAWINGS OF THE AREA THAT IS |
| | CHANGING. FBC 107.2.1 |
| | |
| | 3) PLEASE PROVIDE ENERGY CALCULATIONS BASED ON THE 2020 |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION CODE. FBC EC |
| | C101.5 |
| | |
| | 4) PLEASE PROVIDE VOLUME CALCULATIONS FOR THE |
| | REFRIGERATION. FBC M 1104.4 |
| | |
| | 5) PLEASE SHOW WHERE THE CONDENSATE DRAIN IS |
| | TERMINATING AT THE EXTERIOR. IT CAN NOT GO TO THE |
| | SEWER. FBC M 307.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |