| Notes |
| Date |
Text |
| 2021-02-01 13:39:14 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | PERMIT DESCRIPTION HAS BEEN CORRECTED TO (BUILDING A | | | NEW WORKSHOP). | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FS 553.73, THE PERMIT WAS APPLIED FOR ON JANUARY 27, | | | 2021, THEREFORE THE FOLLOWING SECTIONS OF SUBMITTED | | | PLANS MUST BE CORRECTED TO INDICATE THE CORRECT CODE, | | | WHICH IS FLORIDA BUILDING CODE 2020 7TH EDITION: | | | SHEET #1, GENERAL NOTES AND CODES, SHEET #2, GENERAL | | | STRUCTURAL NOTES AND DESIGN LOADS, SHEET #3 PRIMARY | | | OUTPUT FORM. | | | | | | 2) FBC B 107.2, PROVIDE PRODUCT APPROVALS FOR PROPOSED | | | WINDOW AND DOOR. | | | | | | 3) FBC B 107.2, CLARIFY TYPE AND R-VALUE OF INSULATION | | | ABOVE CEILING ON SHEET #6 (EXAMPLE R-30). | | | |
|