| 2021-05-11 14:13:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21011007 630 S SAPODILLA AVE # 315 |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | NOTE: PER WPB FBC 105.1, A PLUMBING SUB-PERMIT IS |
| | REQUIRED. |
| | |
| | 1.NEW COMMENT: FALLS UNDER THE RULES OF THE FAIR |
| | HOUSING ACT. IN ACCORDANCE WITH WPB FBC 107.2.1, |
| | INDICATE ON THE FLOOR PLAN, COMPLIANCE WITH THE FAIR |
| | HOUSING ACT, INDICATING TYPE OF BATHROOM(S), (TYPE A, |
| | TYPE B), IN ACCORDANCE WITH GUIDELINES UNDER |
| | REQUIREMENT 7, INCLUDING CLEAR FLOOR SPACE AND |
| | MANEUVERING. IF NON-COMPLIANT YOU MAY SUBMIT A REQUEST |
| | FOR WAIVER IN THE FORM OF A LETTER SHOWN BELOW. THIS |
| | SHOULD BE SIGNED BY BOTH PARTIES (DESIGNER AND OWNER), |
| | BUT ONLY THE OWNER?S SIGNATURE NEEDS TO BE NOTARIZED. |
| | |
| | PROJECT ADDRESS: ______________________________________ |
| | _____________________ |
| | PERMIT NUMBER: ________________________ |
| | THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| | PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS |
| | OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER |
| | AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF |
| | SALE IF SO REQUESTED BY THE BUYER. |
| | |
| | SIGNATURE OF DESIGNER: ______________________________ |
| | PRINTED NAME OF DESIGNER: ___________________________ |
| | |
| | SIGNATURE OF OWNER: ________________________________ |
| | PRINTED NAME OF OWNER: _____________________________ |
| | NOTARY FOR OWNER?S SIGNATURE: |
| | STATE OF FLORIDA, COUNTY OF PALM BEACH |
| | THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| | THIS _____ DAY OF ________, 20__ BY |
| | ___________________________ WHO IS PERSONALLY KNOWN TO |
| | ME OR WHO HAS PRODUCED: ___________________________ AS |
| | IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| | NOTARY SIGNATURE ___________________________________ |
| | NOTARY PRINTED NAME ________________________________ |
| | |
| | |
| | |
| | |
| | 2.1 SECOND REQUEST: PER WPB FBC 107.3.4.3 CERTIFICATION |
| | BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DREW THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. THE |
| | PLUMBING CONTRACTOR SHALL PROVIDE A DRAWING(S) WITH |
| | PRINTED NAME, SIGNATURE AND LICENSE NUMBER. |
| | |
| | 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING: 1) A SANITARY AND WATER RISER DIAGRAM |
| | ADDRESSING NEW DOUBLE VANITY AND 2) PROVIDE WALL, CURB, |
| | LINER AND DRAIN DETAIL SHOWING COMPLIANCE WITH FBC PL |
| | 421.5.2.1 THROUGH 421.5.2.6. SEE BELOW. |
| | 421.5.1SUPPORT. |
| | FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| | LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| | SOUND BASE. |
| | 421.5.2SHOWER LINING. |
| | FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE |
| | PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE |
| | LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING |
| | WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6. SUCH LINERS |
| | SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 |
| | MM) ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE |
| | RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT |
| | TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND |
| | SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS |
| | THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD. |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO |
| | THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A |
| | WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE |
| | COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH |
| | SECTION 312.9. |
| | 421.5.2.1PVC SHEETS. |
| | PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL MEET |
| | THE REQUIREMENTS OF ASTM D4551. SHEETS SHALL BE JOINED |
| | BY SOLVENT WELDING IN ACCORDANCE WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | 421.5.2.2CHLORINATED POLYETHYLENE (CPE) SHEETS. |
| | NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL |
| | MEET THE REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE |
| | JOINED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. |
| | 421.5.2.3SHEET LEAD. |
| | SHEET LEAD SHALL WEIGH NOT LESS THAN 4 POUNDS PER |
| | SQUARE FOOT (19.5 KG/M2) AND SHALL BE COATED WITH AN |
| | ASPHALT PAINT OR OTHER APPROVED COATING. THE LEAD SHEET |
| | SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER |
| | THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT |
| | FELT OR AN EQUIVALENT. SHEET LEAD SHALL BE JOINED BY |
| | BURNING. |
| | 421.5.2.4SHEET COPPER. |
| | SHEET COPPER SHALL CONFORM TO ASTM B152 AND SHALL WEIGH |
| | NOT LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M2). |
| | THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING |
| | SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND |
| | (6.80 KG) ASPHALT FELT OR AN EQUIVALENT. SHEET COPPER |
| | SHALL BE JOINED BY BRAZING OR SOLDERING. |
| | 421.5.2.5SHEET-APPLIED, LOAD-BEARING, BONDED, |
| | WATERPROOF MEMBRANES. |
| | SHEET-APPLIED, LOAD-BEARING, BONDED, WATERPROOF |
| | MEMBRANES SHALL MEET REQUIREMENTS OF ANSI A118.10 AND |
| | SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. |
| | 421.5.2.6LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING, |
| | BONDED WATERPROOF MATERIALS. |
| | LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING, BONDED |
| | WATERPROOF MATERIALS SHALL MEET THE REQUIREMENTS OF |
| | ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH |
| | THE MANUFACTURER'S INSTRUCTIONS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER |
| | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |