2021-03-23 14:17:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21011007 630 S SAPODILLA AVE # 315
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 1.PER WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. THE PLUMBING CONTRACTOR
 SHALL PROVIDE A DRAWING(S) WITH PRINTED NAME, SIGNATURE
 AND LICENSE NUMBER.
  
 2.PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING:FLOOR PLAN
 OF BATHROOMS, SANITARY AND WATER RISER DIAGRAM
 ADDRESSING NEW DOUBLE VANITY AND PROVIDE WALL, CURB,
 LINER AND DRAIN DETAIL SHOWING COMPLIANCE WITH FBC PL
 421.5.2.1 THROUGH 421.5.2.6.
 421.5.1SUPPORT.
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 421.5.2SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6. SUCH LINERS
 SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51
 MM) ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE
 COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH
 SECTION 312.9.
 421.5.2.1PVC SHEETS.
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL MEET
 THE REQUIREMENTS OF ASTM D4551. SHEETS SHALL BE JOINED
 BY SOLVENT WELDING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 421.5.2.2CHLORINATED POLYETHYLENE (CPE) SHEETS.
 NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL
 MEET THE REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE
 JOINED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
 421.5.2.3SHEET LEAD.
 SHEET LEAD SHALL WEIGH NOT LESS THAN 4 POUNDS PER
 SQUARE FOOT (19.5 KG/M2) AND SHALL BE COATED WITH AN
 ASPHALT PAINT OR OTHER APPROVED COATING. THE LEAD SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET LEAD SHALL BE JOINED BY
 BURNING.
 421.5.2.4SHEET COPPER.
 SHEET COPPER SHALL CONFORM TO ASTM B152 AND SHALL WEIGH
 NOT LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M2).
 THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING
 SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND
 (6.80 KG) ASPHALT FELT OR AN EQUIVALENT. SHEET COPPER
 SHALL BE JOINED BY BRAZING OR SOLDERING.
 421.5.2.5SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANES.
 SHEET-APPLIED, LOAD-BEARING, BONDED, WATERPROOF
 MEMBRANES SHALL MEET REQUIREMENTS OF ANSI A118.10 AND
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
 421.5.2.6LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING,
 BONDED WATERPROOF MATERIALS.
 LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING, BONDED
 WATERPROOF MATERIALS SHALL MEET THE REQUIREMENTS OF
 ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH
 THE MANUFACTURER?S INSTRUCTIONS.
  
 3. SEE BUILDING EXAMINER?S COMMENT. POST TENSION SLAB/
 NEW HOLES. THE PLAN IS SILENT AS IF THE LOCATION OF THE
 EXISTING TUB DRAIN IS GOING TO BE REUSED IN THE SAME
 LOCATION. IF NOT, THEN THE FLOOR SLAB WILL NEED TO BE
 X-RAYED TO FIND THE POST TENSION CHORD LOCATIONS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 4. SEE BUILDING EXAMINER?S COMMENT.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES).
 IF A NEW FLOOR PENETRATION IS MADE FOR THE FUTURE
 SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-B SECTION 714.5.1.2. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH
 PENETRATIONS SHALL BE PROTECTED BY A THROUGH
 PENETRATION FIRESTOP SYSTEM INSTALLED IN ACCORDANCE
 WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL HAVE AN F
 RATING / T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER
 PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  