| 2021-03-19 10:48:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21011007 |
| | ADD: 630 S. SAPODILLA AVE. # 315 |
| | CONT: BUILDING DESIGN INC. |
| | TEL: 561-612-4300 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 19, 2021 |
| | ACTION: DENIED |
| | |
| | 1) THE FLOOR PLAN SUBMITTED BY BUILDING DESIGN INC. MAY |
| | HAVE THE COMPANY NAME ON THE PLAN BUT NOT THE QUALIFIER |
| | OF THE COMPANY. THE CONTRACTOR (QUALIFIER) THAT CREATED |
| | / DREW THE SET OF PLANS WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 2) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS |
| | IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO |
| | BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| | SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| | CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). |
| | IF A NEW FLOOR PENETRATION IS MADE FOR THE FUTURE |
| | SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE WITH THE |
| | 2020 FBC-B SECTION 714.5.1.2. THROUGH-PENETRATIONS |
| | FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY A THROUGH |
| | PENETRATION FIRESTOP SYSTEM INSTALLED IN ACCORDANCE |
| | WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL HAVE AN F |
| | RATING / T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS |
| | THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. |
| | |
| | 4) MISSING INFORMATION ON PLANS. |
| | 4A) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| | A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 4B) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |