Plan Review Notes
Plan Review Notes For Permit 21010992
Permit Number 21010992
Review Stop P
Sequence Number 3
Notes
Date Text
2021-06-29 15:55:2321010992 1225 PALM BEACH LAKES BLVD
  
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 A SEPARATE SUB PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR
  
 A SEPARATE SUB PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS.
  
2021-06-29 10:35:19HOLD FOR REVISED DRAWINGS FROM ENGINEER
2021-06-24 15:47:13PLUMBING
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21010992 1225 PALM BEACH LAKES BLVD
  
 3RD REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1.PROVIDED GREASE INTERCEPTOR DETAIL GS-7 ON P-8 DOES
 NOT CORRESPOND WITH THE WPB PUBLIC WORKS DEPT. STANDARD
 DETAIL GS-7 (CONCRETE) FOR GREASE INTERCEPTOR IN MY
 FILES. I WILL FORWARD PDF GS-7 GREASE INTERCEPTOR
 REDLINED FOR YOUR USE IN PREPARING A REVISED SUBMITTAL
 TO [email protected], [email protected] AND
 [email protected]. I APOLOGIZE IF THERE WAS A
 MISCOMMUNICATION ON MY PART REGARDING THE STANDARD
 DETAIL.
 IT IS NOTED THE GREASE TRAP CALCULATIONS HAVE BEEN
 INCLUDED ON P8.0.
  
 2.ADDITIONALLY, PER WPB PUBLIC WORKS DEPT. CONCRETE
 GRAVITY SEWER SYSTEM-GREASE INTERCEPTOR STANDARD DETAIL
 GS-7-NOTE 4, A CONCRETE GREASE INTERCEPTOR SHALL HAVE A
 MINIMUM 750 GALLON/ MAXIMUM 1250 GALLON CAPACITY. WHEN
 REQUIRED EFFECTIVE CAPACITY IS GREATER THAN 1250
 GALLONS, PROVIDE A MULTI-CHAMBERED INTERCEPTOR OR
 MULTIPLE INTERCEPTORS INSTALLED IN SERIES. P8.0 AND
 P1.0 CALL FOR A 1500 GALLON INTERCEPTOR.
  
  
  
 3.REGARDING SUBMITTED CIVIL DRAWINGS; NOTE C-10 UTILITY
 PLAN INDICATES 6 INCH GREASY WASTE INTO AND OUT OF THE
 GREASE INTERCEPTOR AND A 6 INCH BUILDING SEWER; P1.0AND
 P5.0 INDICATE ALL 4 INCH SIZING. PER WPB FBC 107.2.1,
 RECONCILE CIVIL AND PLUMBING PLANS.
  
 4. RESPONSE: TRAP PRIMER SHALL BE SPECIFIED AND
 DETAILED. THE TRAP PRIMER IS SPECIFIED ON P1.0 WITH THE
 FLOOR DRAIN FD-1. SEE DETAIL 1, SHEET P7.0.
 P1.0 IS COMPLIANT. SHEET P7.0 IS NOT IN THE NEW
 SUBMITTALS.
  
 5. RESPONSE: CONDENSATE DRYWELL IS INDICATED ON P2.0
 KEYNOTE 15 AND DETAILED ON P7.0 DETAIL #2.
 P1.0 IS COMPLIANT. SHEET P7.0 IS NOT IN THE NEW
 SUBMITTALS.
  
 6.RESPONSE: FLOOR SINK IS IDENTIFIED ON P2.0 NEXT TO
 S-4 AND P4.0 IN THE SAME LOCATION.
 NOTED ON P2.0 AND P4.0; ISSUE IS ON P5.0 WHICH HAS S-4
 AND S-2 IN OPPOSITE LOCATIONS FROM THAT ON P2.0 AND
 P4.0. PER WPB FBC 107.2.1, CORRECTLY IDENTIFY ON P5.0,
 S-2 AND S-4.
  
 8.REGARDING RESPONSE: 6? GREASE WASTE REFERENCE SHALL
 BE REVISED TO 4?
 SECOND REQUEST: PER WPB FBC 107.2.1, ON P5.0, SHOW
 SIZE(S) OF SANITARY AND GREASY WASTE BUILDING DRAINS.
  
  
 9. RESPONSE: HEAT TRACE PIPING IS SPECIFIED ON P2.0,
 KEYNOTE #7. THE DETAIL IS ON P7.0, DETAIL #3.
 P2.0 SPECIFICATION IS NOTED. SHEET P7.0 IS NOT IN THE
 NEW SUBMITTALS; NOTHING NOTED REGARDING INSULATION.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS.