Plan Review Notes
Plan Review Notes For Permit 21010992
Permit Number 21010992
Review Stop G
Sequence Number 3
Notes
Date Text
2021-06-29 15:59:3621010992 1225 PALM BEACH LAKES BLVD
  
  
 GAS COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 COMBUSTION AIR CALCULATIONS PROVIDED ON M-2.0
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR FURTHER
 INFORMATION
  
 THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE AT JOB SITE FOR FINAL GAS
 INSPECTION
  
 A GAS SUB PERMIT IS REQUIRED
2021-06-29 10:34:18HOLD FOR REVISED DRAWINGS FROM ENGINEER
2021-06-24 16:04:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21010992 1225 PALM BEACH LAKES BLVD
  
 3RD REVIEW
  
 GAS COMMENTS: DENIED
  
 1. PREVIOUS REQUEST: PER WPB FBC 107.2.1, SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER FBC FG 304.1. THIS
 IS NOT TO BE CONFUSED WITH MAKE-UP AIR. RESPONSE FROM
 ENGINEER; COMBUSTION AIR TO BE PROVIDED VIA DIRECT
 VENT. KEYNOTE 14 (THE NOTE IS 13) ON WASTE AND VENT
 PLAN P2.0 HAS BEEN REVISED TO REFLECT THIS. THIS
 ADDRESSES COMBUSTION AIR FOR THE TANKLESS WATER HEATERS
 BUT DOES NOT ADDRESS THE APPLIANCES ON THE COOKING
 LINE. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR
 COMBUSTION AIR PER FBC FG 304.1. THIS IS NOT TO BE
 CONFUSED WITH MAKE-UP AIR.
  
 RESPONSE: PER FBC FG 304.9, THE 455,000 BTU/H COOKING
 LINE REQUIRES 159.25 CFM OF MECHANICALLY SUPPLIED
 COMBUSTION AIR. THIS REQUIREMENT IS MET BY THE KITCHEN
 RTU PROVIDING 770 CFM OF OUTDOOR AIR TO THE SPACE.
  
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE THIS
 INFORMATION ON THE PLANS.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS.
  