Plan Review Notes For Permit 21010992
Permit Number 21010992
Review Stop P
Sequence Number 2
Notes
Date Text
2021-05-25 15:06:51PLUMBING
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21010992 1225 PALM BEACH LAKES BLVD
  
 2ND REVIEW
 GENERAL NOTES
 A SEPARATE PLUMBING SUB-PERMIT IS REQUIRED FOR THE
 GREASE INTERCEPTOR. A PLAN WITH DETAIL OF THE GREASE
 INTERCEPTOR TO BE INSTALLED AND REQUIRED CONNECTIONS
 COMPLYING WITH CITY OF WEST PALM BEACH PUBLIC WORKS
 DEPARTMENT AND FBC PL SECTION 1003 SHALL BE SUBMITTED.
 SEE WPB PUBLIC WORKS DEPT. STANDARD DETAIL GS-7
 (CONCRETE) AND GS-7.1 (HYDRO-MECHANICAL) FOR GUIDE.
 PLEASE INCLUDE THE GREASE TRAP CALCULATIONS ON THE SAME
 PAGE IN THE SUBMITTAL.
 A SEPARATE PLUMBING SUB-PERMIT IS REQUIRED FOR THE
 BACKFLOW PREVENTOR.
  
 PLUMBING COMMENTS: DENIED
 1.SECOND REQUEST: PER FBC ACC 609.4, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP (NOT THE CENTER) OF THE GRIPPING SURFACE
  
 2.GENERAL COMMENT; PER WPB FBC 107.2.1, PLAN DRAWINGS
 P2.0 AND P3.0 SHALL BE CONFIGURED AND RECONCILED WITH
 COINCIDING RISER DIAGRAMS ON P5.0. COMPLIED
 NEW COMMENT; P5.0 CORRECTLY SHOWS THE MEN?S TOILET ROOM
 WITH THE URINAL CONNECTING TO THE BUILDING DRAIN
 DOWNSTREAM OF THE WATER CLOSET, LAVATORY AND FLOOR
 DRAIN. P2.0 APPEARS TO SHOW THE WATER CLOSET
 DISCHARGING TO THE BUILDING DRAIN WITH THE URINAL
 SERVING AS THE VENT AND ALSO CONNECTING TO THE BUILDING
 DRAIN WITH THE LAVATORY WET VENTING IT AND THE FLOOR
 DRAIN (AS SHOWN ON P5.0). PER WPB FBC 107.2.1, CLARIFY.
  
 3.PLAN SHEET P1.0
 SECOND REQUEST: PER WPB FBC 107.2.1, SUBMIT SITE PLANS.
 TO BE CLEAR, CIVIL DRAWINGS SHOWING SEWER AND WATER ARE
 REQUIRED.
 SECOND REQUEST: PER WPB FBC 107.2.1, SPECIFY THE TRAP
 PRIMER AND PROVIDE A DETAIL FOR THE TRAP PRIMER.
  
 4. PLAN SHEET P2.0
 SECOND REQUEST: PROVIDE DETAIL FOR CONDENSATE DRYWELL
  
 5.P4.0
 NEW COMMENT: REGARDING S-4 PEDESTAL SINK; ENGINEER
 RESPONSE IS THAT SINK IS FOR FOOD PREP (NOTED ON
 REVISED SCHEDULE P1.0) AND THAT THE DRAIN IS REVISED TO
 A FLOOR SINK CONNECTION. PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWING:
 IDENTIFY THE FLOOR SINK ON P2.0 AND P5.0
 PROVIDE A DETAIL OF THE SINK, FLOOR SINK AND SIZED
 INDIRECT WASTE THROUGH AN AIR GAP SHOWING COMPLIANCE
 WITH FBC PL 802.1.1
 ON P1.0 FIXTURE SCHEDULE INDICATE INDIRECT FOR WASTE
  
 6.P6.0
 NEW COMMENT: PER WPB FBC 107.2.1, INDICATE ON P6.0,
 DETAIL 3 THAT THE FOOT PEDAL IS FOR S-4 OR ON P1.0, S-4
 DESCRIPTION , ADD FOOT PEDALS AND REFER TO P6.0/DETAIL
 3.
  
 7.SEE PLAN SHEET A3.0:
 SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE
 CALCULATIONS AND SIZING FOR VERTICAL LEADERS AND
 HORIZONTAL GUTTERS. TO BE CLEAR, SHOW THE CALCULATIONS
 AND THE SIZING ON THE PLAN. ADDITIONALLY, INDICATE
 SQUARE FOOTAGE AND GPM OF AREAS BEING DRAINED AND
 INDICATE ON THE PLAN, GUTTER AND DOWNSPOUT SIZE. NOTES
 11, 13 AND 14 ON A3.0 ARE ACKNOWLEDGED.
 NEW COMMENT: AS THERE IS NO STORM PIPING IN THE
 BUILDING, PER WPB FBC 107.2.1, DELETE REFERENCES TO
 STORM PIPING, ROOF DRAINS, OVERFLOW DRAINS, DOWNSPOUT
 NOZZLES, ETC. IN THE FIXTURE SCHEDULE(P1.0) AND WASTE &
 VENT NOTES (P2.0).
  
 NEW COMMENTS:
  
 1. P5.0 INDICATES 6 INCH GREASY WASTE IN THE WASTE/VENT
 LINE LEGEND. WILL THE GREASE INTERCEPTOR COME FROM THE
 MANUFACTURER WITH INLETS/OUTLETS SIZED TO ACCOMMODATE
 THE 6 INCH DRAIN; WILL THE CIVIL DRAWINGS BE SIZED TO
 RECEIVE SAID SIZE. ADDITIONALLY, P1.0 PLUMBING FIXTURE
 SUMMARY INDICATES 4 INCH GREASY WASTE AS WELL AS 4 INCH
 SANITARY WASTE. PER WPB FBC 107.2.1, CLARIFY. PER WPB
 FBC 107.2.1, ON P5.0, SHOW SIZE(S) OF SANITARY AND
 GREASY WASTE BUILDING DRAINS.
  
 2. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 3. REGARDING S-3 THREE-COMPARTMENT SINK; IDENTIFY IN
 FIXTURE SCHEDULE DESCRIPTION IF THIS IS FOOD PREP OR
 POT WASH. IF FOOD PREP, PROVIDE A DETAIL OF THE
 THREE-COMPARTMENT SINK, FLOOR SINK AND SIZED INDIRECT
 WASTE PIPES THROUGH AN AIR GAP SHOWING COMPLIANCE WITH
 FBC PL 802.1.1. EACH WELL OF A MULTIPLE-COMPARTMENT
 SINK SHALL DISCHARGE INDEPENDENTLY TO THE WASTE
 RECEPTOR.
  
 4. PER WPB FBC 107.2.1, AS A KITCHEN EQUIPMENT PLUMBING
 FIXTURES NOTED ON P1.0 FIXTURE SCHEDULE (S-1, S-2, S-3
 AND S-4) ARE INCOMPLETE IN DESCRIPTION, PROVIDE NOTE
 FOR SAID ITEMS, REFERRING TO A2.1 EQUIPMENT SCHEDULE;
 SINKS AND DISHWASHERS FOR FAUCETS/ACCESSORIES (I.E.
 FAUCET FOR S-2) INFORMATION.
  
  
 5. P2.0 NOTE 9. PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION, POWER SOURCE AND DETAIL FOR HEAT TRACE.
 YOU CALL FOR HEAT TRACE APPLIED TO UNDERGROUND GREASY
 WASTE BELOW FREEZER/COOLER BUT DON?T CALL OUT ANY SORT
 OF INSULATION. PER WPB FBC 107.2.1, CLARIFY.
  
 6. P2.0 NOTE 12. DETAIL DESCRIBED IS NOT SHOWN. PER WPB
 FBC 107.2.1, CLARIFY.
  
 7. PER WPB FBC 107.2.1, PROVIDE A DETAIL OF THE
 BACKFLOW PREVENTER (BFP-1). INCLUDE SUPPORTS, STRAINER,
 RELIEF VENT DISCHARGE PIPING WITH AIR GAP TO FLOOR SINK
 OR HUB DRAIN (TO SANITARY, NOT GREASY WASTE). COMPLY
 WITH MANUFACTURER?S RECOMMENDATIONS PER FBC PL 301.7.
 SEE EXCERPTS FROM WATTS INSTALLATION, MAINTENANCE, &
 REPAIR SERIES 009 AND LF009 REDUCED PRESSURE ZONE
 ASSEMBLIES RP/IS-009 BELOW
 A.INDOORS ? FIGURE 1 FOR INDOOR INSTALLATIONS, IT IS
 IMPORTANT THAT THE ASSEMBLY BE EASILY ACCESSIBLE TO
 FACILITATE TESTING AND SERVICING. IF IT IS LOCATED IN A
 LINE CLOSE TO A WALL, BE SURE THE TEST COCKS ARE EASILY
 ACCESSIBLE. A DRAIN LINE AND AIR GAP (SEE LITERATURE
 ES-AG/EL/TC) SHOULD BE PIPED FROM THE RELIEF VALVE
 CONNECTION AS SHOWN, WHERE EVIDENCE OF DISCHARGE WILL
 BE CLEARLY VISIBLE AND SO THAT WATER DAMAGE WILL NOT
 OCCUR. THEREFORE, NEVER INSTALL IN CONCEALED LOCATIONS.
 B.WE RECOMMEND A STRAINER BE INSTALLED AHEAD OF 009 AND
 LF009 SERIES ASSEMBLIES TO PROTECT THE INTERNAL
 COMPONENTS FROM UNNECESSARY FOULING.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS.