| 2021-03-30 13:38:49 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21010992 1225 PALM BEACH LAKES BLVD |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | |
| | 1.FBC ACC COMMENTS |
| | A.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | B.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT |
| | THE CENTER) OF THE GRIPPING SURFACE |
| | |
| | 2.AS THERE IS NO DRINKING FOUNTAIN PROVIDED, IT IS |
| | NOTED THAT PER FBC PL 410.4, WHERE RESTAURANTS PROVIDE |
| | DRINKING WATER IN A CONTAINER FREE OF CHARGE, DRINKING |
| | FOUNTAINS SHALL NOT BE REQUIRED IN THOSE RESTAURANTS. |
| | PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE P1.0 GENERAL |
| | NOTES AND A1.0 KEY NOTES STATING "PROVIDE PERMANENT |
| | SIGN AT DRINK DISPENSER AND COUNTER AS FOLLOWS: |
| | DRINKING WATER AND CUP PROVIDED AT NO CHARGE" |
| | |
| | 3.GENERAL COMMENT; PER WPB FBC 107.2.1, PLAN DRAWINGS |
| | P2.0 AND P3.0 SHALL BE CONFIGURED AND RECONCILED WITH |
| | COINCIDING RISER DIAGRAMS ON P5.0. |
| | |
| | 4.PLAN SHEET P1.0 |
| | A.NOTE 3 IS CALLING FOR CONTRACTOR TO REVISE SANITARY |
| | TO ACCOMMODATE SANITARY SEWER ON THE SITE PLAN. IT IS |
| | THE DESIGNER'S RESPONSIBILITY TO DETERMINE THE CORRECT |
| | CONFIGURATION OF THE SANITARY BUILDING DRAIN AND GREASY |
| | WASTE/INTERCEPTOR. PER WPB FBC 107.2.1, SUBMIT SITE |
| | PLANS AND ADJUST BUILDING PLUMBING AS REQUIRED TO |
| | RECONCILE. |
| | B.NOTE 4 SHALL READ "PROVIDE TRAP SEAL PROTECTION FOR |
| | ALL FLOOR DRAINS COMPLYING WITH FBC PL 1002.4.1, |
| | 1002.4.1.1, 1002.4.1.2, 1002.4.1.3 AND 1002.4.1.4. DEEP |
| | SEAL TRAPS ARE NOT COMPLIANT." |
| | ADDITIONALLY, PER WPB FBC 107.2.1, SPECIFY THE TRAP |
| | PRIMER AND PROVIDE A DETAIL FOR THE TRAP PRIMER. |
| | C. NOTE 16; ADD TO NOTE THE VERBIAGE "AND AS REQUIRED |
| | BY FBC PL 604.9." |
| | D.NOTE 21- CALLS FOR PROVIDING CONDENSATE DRAINS FOR |
| | ALL A/C UNITS. PER WPB FBC 107.2.1, PROVIDE RISER |
| | DIAGRAM TO CORRESPOND WITH PLAN DRAWINGS ROUTING, |
| | SIZING, TERMINATION. |
| | E.NOTE 22- AS THIS PLAN IS FOR PERMITTING, PLEASE NOTE, |
| | ANY CHANGES TO EQUIPMENT, ETC. WILL REQUIRE REVISED |
| | DRAWINGS WHICH SHALL BE SUBMITTED AND APPROVED PRIOR TO |
| | INSPECTION. PROCCED AT YOUR OWN RISK. |
| | WPB FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| | OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| | THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| | THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| | PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| | PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. THIS LIST SHALL BE |
| | PROVIDED PRIOR TO PERMIT ISSUANCE. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | F.GREASE TRAP CALCULATIONS ARE INCLUDED ON THIS |
| | DRAWING. PLEASE NOTE, A SEPARATE PERMIT IS REQUIRED FOR |
| | THE GREASE INTERCEPTOR. A PLAN WITH DETAIL OF THE |
| | GREASE INTERCEPTOR TO BE INSTALLED AND REQUIRED |
| | CONNECTIONS COMPLYING WITH CITY OF WEST PALM BEACH |
| | PUBLIC WORKS DEPARTMENT AND FBC PL SECTION 1003 SHALL |
| | BE SUBMITTED. SEE WPB PUBLIC WORKS DEPT. STANDARD |
| | DETAIL GS-7 (CONCRETE) AND GS-7.1 (HYDRO-MECHANICAL) |
| | FOR GUIDE. PLEASE INCLUDE THE GREASE TRAP CALCULATIONS |
| | ON THE SAME PAGE IN THE SUBMITTAL. |
| | G. PER WPB 107.2.1, BFP-1 SCHEDULED BACKFLOW PREVENTORS |
| | SHALL BE SPECIFIED BY THEIR LEAD-FREE MODEL NUMBER. |
| | ACTUAL MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL |
| | SHALL BE SUBMITTED, APPROVED, IN PLACE AND PLAN SHALL |
| | BE REVISED TO REFLECT FOR FINAL INSPECTION. SEE COMMENT |
| | 4 (E) NOTE 22. |
| | |
| | 5. PLAN SHEET P2.0 |
| | A. MEN'S RESTROOM: PER FBC PL 912.1, ONLY BATHROOM |
| | GROUP FIXTURES MAY CONNECT TO THE WET VENT. URINAL AND |
| | HAND SINK SHOWN CONNECTED ARE NOT CONSIDERED BATHROOM |
| | GROUP FIXTURES (SEE FBC PL CHAPTER 2, DEFINITIONS, |
| | BATHROOM GROUP). ADDITIONALLY, P5.0 SANITARY RISER |
| | DIAGRAM AND P2.0 DO NOT MATCH. P5.0 SANITARY RISER |
| | DIAGRAM ALSO DOES NOT SHOW THE URINAL UR-1 AND NOTES |
| | MSB-1/S-2, BUT NO S-1 ON P2.0. PER WPB FBC 107.2.1, |
| | CLARIFY AND RECONCILE. SEE COMMENT A. GENERAL COMMENT |
| | B.REGARDING NOTE 1, PER WPB PL 802.4, FOR OTHER THAN |
| | HUB DRAINS THAT RECEIVE ONLY CLEAR-WATER WASTE AND |
| | STANDPIPES (IE. FIRE PROTECTION TEST DRAIN), A |
| | REMOVABLE STRAINER OR BASKET SHALL COVER THE OUTLET OF |
| | WASTE RECEPTORS. IT IS THE DESIGNER?S RESPONSIBILITY TO |
| | DETERMINE WHETHER A HUB DRAIN COMPLIES, OR IF A FLOOR |
| | SINK IS REQUIRED. PER WPB FBC 107.2.1, CLARIFY AND |
| | DESIGNATE ACCORDINGLY. IF THE DRAINS IN QUESTION |
| | RECEIVE ONLY CLEAR WATER WASTE, THEY MAY REMAIN AS HUB |
| | DRAINS; HOWEVER, CLEAR WATER WASTE IS NOT GREASY WASTE |
| | AND AS SUCH SHALL NOT DISCHARGE TO THE GREASY WASTE. |
| | C.REGARDING NOTE 2 AND 5, CONDENSATE FROM A/C |
| | CONDENSATE SHALL NOT DISCHARGE TO THE GREASY WASTE PER |
| | FBC PL 1003.2. ADDITIONALLY, PER WPB CODE OF ORDINANCE |
| | CHAPTER 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE |
| | SHALL NOT DISCHARGE TO THE CITY UTILITIES SANITARY |
| | SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM THE |
| | UTILITIES DEPARTMENT. YOU MAY CONTACT MR. MANNY |
| | GONZALES IN ENGINEERING AT 561-494-1128 FOR ADDITIONAL |
| | INFORMATION. MOVING FORWARD, DISCHARGE THE CONDENSATE |
| | TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1, PROVIDE |
| | ROUTING AND DRYWELL DETAIL. |
| | D.REGARDING NOTE 3, NOTES THAT BEVERAGE UNIT WASTE TO |
| | DISCHARGE TO FLOOR SINK. THE FLOOR SINK INDICATED |
| | DISCHARGES TO THE GREASY WASTE; PER FBC PL 1003.2, |
| | WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION |
| | SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR |
| | SEPARATOR. |
| | E.REGARDING NOTE 4 AND 7, CONDENSATE FROM COOLER |
| | EVAPORATOR SHALL NOT DISCHARGE TO THE GREASY WASTE PER |
| | FBC PL 1003.2. ADDITIONALLY, PER WPB CODE OF ORDINANCE |
| | CHAPTER 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE |
| | (INTERPRET THIS AS ANY CONDENSATION FROM EVAPORATOR |
| | COILS) SHALL NOT DISCHARGE TO THE CITY UTILITIES |
| | SANITARY SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM |
| | THE UTILITIES DEPARTMENT. YOU MAY CONTACT MR. MANNY |
| | GONZALES IN ENGINEERING AT 561-494-1128 FOR ADDITIONAL |
| | INFORMATION. MOVING FORWARD, DISCHARGE THE CONDENSATE |
| | TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1, PROVIDE |
| | ROUTING AND DRYWELL DETAIL. |
| | F.REGARDING NOTE 6, PER WPB FBC 107.2.1, CONFIRM THAT |
| | ALL DRAINS ON THIS RUN ARE ALLOWED TO CONNECT TO GREASY |
| | WASTE AS ALLOWED IN FBC PL 1003.2. |
| | G.REGARDING NOTE 11, NOTES THAT S/S DRINK MACHINE WASTE |
| | TO DISCHARGE TO FLOOR SINK. THE FLOOR SINK INDICATED |
| | DISCHARGES TO THE GREASY WASTE; PER FBC PL 1003.2, |
| | WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION |
| | SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR |
| | SEPARATOR |
| | J.REGARDING NOTE 13, COULD NOT LOCATE ON THE PLAN. |
| | PLEASE CLARIFY. |
| | |
| | 6.P4.0 |
| | A.SINK S-4 IS DESIGNATED A PREP SINK. IS THIS A FOOD |
| | PREP SINK? PLEASE CLARIFY. PROVIDE MANUFACTURER'S DATA |
| | FOR AERO MANUFACTURING PEDESTAL SINK. IF A FOOD PREP |
| | SINK IT MUST DISCHARGE TO A FLOOR SINK THROUGH AN AIR |
| | GAP COMPLYING WITH THE REQUIREMENTS OF FBC PL 802.1.1. |
| | B.MSB-1/S-2 IS INCORRECTLY IDENTIFIED AS S-4 ON P2.0 |
| | AND P4.0 FLOOR PLANS. PER WPB FBC 107.2.1, CLARIFY AND |
| | RECONCILE. |
| | |
| | 7.P5.0 WATER RISER DIAGRAM. SHOW ON COLD/HOT/TEMPERED |
| | WATER DISTRIBUTION BRANCH TO S-287, S-288 WATER |
| | FILTERS. INDICATE TEMPERATURE OF HOT WATER. SHOW |
| | LOCATIONS AND PROVIDE SCHEDULE/SPEC FOR ALL BACKFLOW |
| | PREVENTERS INCLUDING THOSE PROVIDED BY BEVERAGE |
| | DISPENSER PROVIDER. ALL BACKFLOW PREVENTERS SHALL BE |
| | LEAD FREE AND MEET THE REQUIREMENTS OF FBC PL SECTION |
| | 608 FOR THEIR DESIGNATED USE. |
| | |
| | 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE WATER |
| | HEATER(S). WATER HEATER AS SHOWN (PLAN VIEWS SEEM TO |
| | SHOW A TANK TYPE AND TANKLESS; IT IS UNCLEAR) ON P6.0 |
| | DETAIL 9 WATER HEATER SCHEDULE, DETAIL 7 WATER |
| | FILTRATION AND A2.1 EQUIPMENT SCHEDULE ARE |
| | BRADFORD-WHITE EF100T199E3N 100 GALLON STORAGE TANK |
| | TYPE BOTTOM FED. WATER HEATERS PER P1.0 SCHEDULE, P6.0 |
| | WATER HEATER SCHEMATIC AND P5.0 RISER DIAGRAM ARE |
| | TANKLESS. PER WPB FBC 107.2.1, CLARIFY TANK TYPE OR |
| | TANKLESS AND CLEARLY INDICATE ON THE PLANS. |
| | IF TANKLESS WATER HEATERS ARE TO BE USED THEN REMOVE |
| | ALL REFERENCE TO TANK TYPE WATER HEATER. REVISE |
| | APPLICABLE DETAILS AND NOTES TO REFLECT THE TANKLESS |
| | WATER HEATERS. |
| | IF A TANK TYPE WATER HEATER IS THE APPLICABLE WATER |
| | HEATER THEN REMOVE OR REVISE ALL REFERENCE TO TANKLESS |
| | WATER HEATERS. REVISE WATER HEATER SCHEDULE ON P1.0 TO |
| | REFLECT, INCLUDE MANUFACTURER, MODEL, CAPACITY. REVISE |
| | WATER HEATER SCHEMATIC TO REFLECT. INCLUDE |
| | RECIRCULATION PUMP, TEMPERATURE OF THE HOT WATER, CW, |
| | HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE |
| | FBC PL 504.2), THERMAL EXPANSION CONTROL DEVICE |
| | (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION) |
| | AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) |
| | PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, |
| | 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND |
| | 504.7.2. |
| | PLEASE NOTE THAT P3.0, NOTE 18 INDICATES A SINGLE |
| | EXHAUST FOR THE WATER HEATER REFERENCING P6.0, DETAIL |
| | 2. THIS NEEDS TO BE ADDRESSED AND CLARIFIED PER WPB FBC |
| | 107.2.1. |
| | |
| | 9.PER WPB FBC 107.2.1, PROVIDE AN ENGINEERED DETAIL FOR |
| | SUPPORT OF WATER HEATER(S) INCLUDING ANCHORS. |
| | |
| | 10.P6.0 |
| | A. PER WPB FBC 107.2.1, ADVISE AS TO WHAT FIXTURE |
| | DETAIL 3; FOOT PEDAL APPLIES TO. |
| | B. PROVISO: SEE DETAIL 2. PER WPB FBC 107.2.1, THE |
| | MANUFACTURE'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | WATER HEATER VENT UBBINK OR HEAT FAB SAF-T VENT SC |
| | SHALL BE SUBMITTED, APPROVED, IN PLACE AND PLAN SHALL |
| | BE REVISED TO REFLECT FOR FINAL INSPECTION. SEE COMMENT |
| | 4 (E) NOTE 22. |
| | C. DETAIL 7; NOTE 4: PER WPB FBC 107.2.1, SPECIFY LEAD |
| | FREE MODEL FOR BACKFLOW PREVENTER. |
| | |
| | 11. PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION |
| | OF PIPE, VALVES AND FITTINGS FOR ALL PIPING SYSTEMS |
| | INCLUDING BUT NOT LIMITED TO SANITARY, DOMESTIC WATER |
| | AND FILTERED WATER; SHOW COMPLIANCE WITH FBC PL |
| | SECTIONS 607 (PROVIDE AN ADDITIONAL NOTE THAT ALL |
| | MATERIALS SHALL BE LEAD FREE) AND 702. ADDITIONALLY, |
| | PER FBC PL E607.5, PROVIDE INSULATION SPECIFICATION FOR |
| | HOT WATER TO COMPLY WITH FBC EC 607.5 AND C404.4. |
| | |
| | 12.PER WPB FBC 107.2.1, SPECIFY MANUFACTURER, MODEL FOR |
| | MV-1 MIXING VALVE WITH ASSE 1070 COMPLIANT PRODUCT AS |
| | REQUIRED BY FBC PL 419.5. |
| | |
| | 13.SEE PLAN SHEET A3.0: |
| | A.SEE BUILDING REVIEWER'S COMMENTS |
| | 1)PER FBC PL 1106.3, VERTICAL LEADERS SHALL BE SIZED |
| | BASED ON THE FLOW RATE FROM HORIZONTAL GUTTERS OR THE |
| | MAXIMUM FLOW RATE THROUGH ROOF DRAINS. THE FLOW RATE |
| | THROUGH VERTICAL LEADERS SHALL NOT EXCEED THAT |
| | SPECIFIED IN TABLE 1106.3. |
| | 2)PER FBC PL 1106.5, WHERE SCUPPERS ARE USED FOR |
| | PRIMARY ROOF DRAINAGE OR FOR SECONDARY (EMERGENCY |
| | OVERFLOW) ROOF DRAINAGE OR BOTH, THE QUANTITY, SIZE, |
| | LOCATION AND INLET ELEVATION OF THE SCUPPERS SHALL BE |
| | CHOSEN TO PREVENT THE DEPTH OF PONDING WATER ON THE |
| | ROOF FROM EXCEEDING THE MAXIMUM WATER DEPTH THAT THE |
| | ROOF WAS DESIGNED FOR AS DETERMINED BY SECTION 1611.1 |
| | OF THE FLORIDA BUILDING CODE, BUILDING. SCUPPER |
| | OPENINGS SHALL BE NOT LESS THAN 4 INCHES (102 MM) IN |
| | HEIGHT AND HAVE A WIDTH THAT IS EQUAL TO OR GREATER |
| | THAN THE CIRCUMFERENCE OF A ROOF DRAIN SIZED FOR THE |
| | SAME ROOF AREA. THE FLOW THROUGH THE PRIMARY SYSTEM |
| | SHALL NOT BE CONSIDERED WHEN LOCATING AND SIZING |
| | SECONDARY SCUPPERS. |
| | B.PER FBC PL 1106.6, HORIZONTAL GUTTERS SHALL BE SIZED |
| | BASED ON THE FLOW RATE FROM THE ROOF SURFACE. THE FLOW |
| | RATE IN HORIZONTAL GUTTERS SHALL NOT EXCEED THAT |
| | SPECIFIED IN TABLE 1106.6. |
| | C.PER WPB FBC 107.2.1, PROVIDE CALCULATIONS AND SIZING |
| | FOR VERTICAL LEADERS, SCUPPERS AND HORIZONTAL GUTTERS. |
| | |
| | END OF COMMENTS. |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |