| 2021-03-29 11:42:43 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21010992 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1.0: NOTE 10 INDICATES SMOKE DETECTORS ARE |
| | TO BE MOUNTED IN THE RETURN AIR DUCT. PLEASE CHANGE |
| | THIS STATEMENT AS IT DOES NOT MEET THE MECHANICAL CODE |
| | SECTION FBC M 606.2.1. THE SMOKE DETECTOR SHALL BE |
| | INSTALLED ON THE SUPPLY SIDE OF THE AIR HANDLING |
| | SYSTEMS. |
| | |
| | 2) PLEASE PROVIDE A NOTE ON THE DRAWING THAT THE HOODS |
| | AND ALL RELATED SYSTEMS MUST BE SUBMITTED AS A SEPARATE |
| | SUBMITTAL AND MUST HAVE ITS OWN REVIEW AND PERMIT. |
| | |
| | 3) PLEASE REMOVE ALL DRAWINGS ASSOCIATED WITH THE HOOD |
| | FROM THIS SUBMITTAL AS IT WILL BE A STAND ALONE PERMIT |
| | AND REVIEW. AND WILL NOT BE REVIEWED IN THIS SUBMITTAL. |
| | |
| | 4) PLEAS PROVIDE A NOTE ON THE DRAWINGS THAT THE |
| | REFRIGERATION EQUIPMENT MUST BE SUBMITTED AS A SEPARATE |
| | SUBMITTAL AND MUST HAVE ITS OWN REVIEW AND PERMIT. |
| | |
| | 5) PLEASE PROVIDE ENERGY CALCULATIONS FOR THIS PROJECT. |
| | FBC EC C402.1 |
| | |
| | 6) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC C403.2.1 |
| | |
| | 7) SHEET M2.0: IT APPEARS THAT THERE IS A RETURN VERY |
| | CLOSE TO THE HOOD IN THE KITCHEN AREA. PLEASE SHOW THAT |
| | THIS RETURN MEETS THE 10 FT. MINIMUM AWAY FROM THE |
| | COOKING APPLIANCES. FBC M 601.5 EXCEPTION (1). |
| | |
| | 8) SHEET M2.1: PLEASE SHOW THE ROOF ACCESS ON THE |
| | MECHANICAL ROOF DRAWING. FBC M 306.5 |
| | |
| | 9) SHEET M2.1: PLEASE SHOW THAT THE MECHANICAL ON THE |
| | ROOF MEETS THE 10 FEET FROM THE ROOFS EDGE OR THE |
| | REQUIRED GUARDS ARE USED. FBC M 307.11 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |