| Date |
Text |
| 2021-03-30 14:46:56 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21010992 1225 PALM BEACH LAKES BLVD |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1.PLEASE NOTE THAT P3.0, NOTE 18 INDICATES A SINGLE |
| | EXHAUST FOR THE WATER HEATER REFERENCING P6.0, |
| | DETAIL.THIS NEEDS TO BE ADDRESSED AND CLARIFIED PER WPB |
| | FBC 107.2.1. |
| | |
| | 2.REGARDING GAS SUPPLIED KITCHEN EQUIPMENT: KITCHEN |
| | EQUIPMENT SCHEDULE ON PLAN SHEET A2.1, GAS EQUIPMENT |
| | SCHEDULE AND GAS RISER DIAGRAM ON PLAN SHEET P5.0 DO |
| | NOT MATCH. A2.1 C COOKING EQUIPMENT SCHEDULE INDICATES |
| | ONE EACH (1) C-018, TWO EACH (2) C-025 AND ONE EACH (1) |
| | C-130. PER WPB FBC RECONCILE THIS SCHEDULE WITH THE GAS |
| | DEMAND SCHEDULE ON P5.0. ADDITIONALLY, RECONCILE RISER |
| | DIAGRAM AND GAS DEMAND SCHEDULE. |
| | |
| | 3.PROVISO: SEE DETAIL 2. PER WPB FBC 107.2.1, THE |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | WATER HEATER VENT UBBINK OR HEAT FAB SAF-T VENT SC |
| | SHALL BE SUBMITTED, APPROVED, IN PLACE AND PLAN SHALL |
| | BE REVISED TO REFLECT FOR FINAL INSPECTION. |
| | |
| | 4.PLEASE SEE PLUMBING COMMENTS. PLANS SHOW BOTH |
| | TANKLESS WATER HEATERS AND A TANK TYPE WATER HEATER. |
| | PER WPB FBC 107.2.1, THIS NEEDS TO BE CLARIFIED AND |
| | RECONCILED. |
| | |
| | 5. PER WPB FBC 107.2.1, SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| | EHD NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE. |
| | |
| | 6.TYPE OF GAS APPEARS TO BE NATURAL. PER WPB FBC |
| | 107.2.1, INDICATE ON GAS DEMAND SCHEDULE. |
| | |
| | 7. PER WPB FBC 107.2.1, PROVIDE TABLE(S) FOR SIZING OF |
| | PIPING. REFER TO FBC FG 401.8, 402.2, AND TABLES 402.4 |
| | (1) THRU 402.4. |
| | |
| | 8. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR PER FBC FG 304.1. THIS IS NOT TO BE |
| | CONFUSED WITH MAKE UP AIR. |
| | |
| | 9. PER WPB FBC 107.2.1, SUBMIT A DETAIL SHOWING THE |
| | TYPE, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| | FBC FG 502 THRU 505. |
| | |
| | 10. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER'S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC FG 402.2, AND 301.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION PER FBC FG 305.1. |
| | |
| | 11.EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| | SECS. 10.4, 10.5 OF NFPA 96-08. PER WPB FBC 107.2.1, |
| | IDENTIFY ON RISER DIAGRAM AND PROVIDE A DETAIL. |
| | |
| | |
| | END OF COMMENTS. |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |