Plan Review Notes
Plan Review Notes For Permit 21010986
Permit Number 21010986
Review Stop Z
Sequence Number 2
Notes
Date Text
2021-03-02 13:28:43FAILED
  
 REPEAT COMMENT - THE PALM BEACH OUTLETS REQUIRE THAT
 ROOFTOP MECHANICAL EQUIPMENT MUST BE SCREENED. PROVIDE
 SIGHTLINE DRAWINGS OR OTHER VERIFICATION THAT THE NEW
 ROOFTOP EQUIPMENT WILL BE SCREENED FROM THE PROPERTY
 LINES TO THE EAST AND SOUTH SIDES OF THE BUILDING.
  
 THANK YOU FOR PROVIDING PHOTOGRAPHS OF THE ROOF AND THE
 BUILDING; HOWEVER, NO INFORMATION WAS PROVIDED ON THE
 HEIGHT OF THE EQUIPMENT TO VERIFY THAT IT IS A LOWER
 HEIGHT THAN THE EXISTING PARAPET WALLS (WHICH WOULD BE
 SCREENED). IF THE EQUIPMENT IS TALLER THAN THE PARAPET
 WALLS, THEN YOU NEED TO PROVIDE EVIDENCE THAT THE
 LOCATION OF THE EQUIPMENT IN RELATIONSHIP TO THE EDGE
 OF THE BUILDING AND THE PARAPET WALLS VERIFIES THAT IT
 WOULD BE SCREENED. PHOTOS CAN SHOW THIS IF YOU HAVE
 INSTALLED A MOCK UP ON THE ROOF IN THE EXACT LOCATION
 OF THE NEW EQUIPMENT. THE PHOTOS, NOT EVEN SHOWING
 WHERE THE NEW EQUIPMENT IS PROPOSED, PROVIDE NO
 VERIFICATION THAT THE NEW EQUIPMENT WILL COMPLY WITH
 THE SCREENING REQUIREMENTS. YOU HAVE NOT PROVIDED PROOF
 THAT THE NEW ROOFTOP EQUIPMENT WILL MEET THE SCREENING
 REQUIREMENTS.
  