| 2021-02-02 15:57:04 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21010986 |
| | 2/2/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A GAS RISER DRAWING IN ACCORDANCE WITH |
| | SECTION 107.3.5.1.5 WPB. PROVIDE THE FOLLOWING |
| | INFORMATION ON THE RISER PER THE FBC FG: |
| | A) TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM- SECTION |
| | 402.2 |
| | B) TOTAL DEVELOPED LENGTH FROM THE METER TO THE MOST |
| | REMOTE OUTLET- 402.4.1. |
| | C) DELIVERY PRESSURE AT THE METER- 401.7. |
| | D) PIPE SIZING TABLES OR SIZING METHOD USED- 402.3 |
| | E) MAIN SUPPLY PIPE SIZE AND BRANCH PIPE POINTS OF |
| | CONNECTION- 401.4 & 402.2. THE DETAIL ON SHEET P101 |
| | APPEARS TO SHOW THE 1 IN. METALLIC DOAS SUPPLY PIPE |
| | CONNECTING TO THE EXISTING 1-1/2 IN. PIPE WHICH IS |
| | CURRENTLY SUPPLYING A LOAD OF 2722 CFH. BASED ON TABLE |
| | 402.4(5) FBC FG THE 1-1/2 IN PIPE IS UNDERSIZED FOR THE |
| | NEW LOAD OF 3322 CFH AT A TOTAL DEVELOPED LENGTH OF 300 |
| | FT. |
| | |
| | 2) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |