| 2021-02-12 13:32:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS ARE A COPY OF THE PREVIOSULY |
| | APPROVED GENERAL CONSTRUCTION PROJECT AND ARE NOT |
| | APPROVED FOR THE HOOD SYSTEM. |
| | |
| | PLEASE SUBMIT JUST THE HOOD SYSTEM PLAN SHEETS AND |
| | REMOVE THE REMIANDER, |
| | |
| | |
| | 1A) THE HOOD SYSTEM DESIGN SHEETS ARE INDICATED AS |
| | BEING FROM CAPTIVEAIRE. |
| | |
| | PLEASE PROVIDE DOCUMENTATION FROM CAPTIVEAIRE THAT YOU |
| | ARE AUTHORIZED TO USE THEIR DESIGN DOCUMENTS. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF ROOF PENETRATIONS |
| | DESIGNS, TRUSS/CEILING DETAILS, CLEARANCE DIMENSIONS, |
| | VOID FILLERS, HANGERS, BRACING, ETC. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS |
| | |
| | |
| | |
| | 3) THERE NO SPECIFIC DETAIL SHOWING THAT THE PROPOSED |
| | EQUIPMENT FITS UNDER THE PROPOSED HOOD INCLUDING THE |
| | TOTAL DIMENSIONS OF ALL THE EQUIPMENT PROPOSED VS THE |
| | HOOD, THAT INCLUDES REQUIRED HOOD END OVERLAP. |
| | |
| | SHEET M104 INDICATES A WOK IN THE MIDDLE AND BROILER ON |
| | THE LEFT; HOWEVER, NEITHER IS ON THE EQUIPMENT LIST. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DIMENSION AND |
| | DETAIL. |
| | |
| | |
| | |
| | 4) THERE IS NO ROOF TOP DETAIL SHOWING ALL EXISTING |
| | EQUIPMENT/OPENING & DIMENSIONS IN COMPLIANCE WITH CODE |
| | REQUIRMENTS. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |