| 2021-04-01 11:29:56 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21010946 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE MORE DETAIL FOR THE STEEL PIPING |
| | LOCATED OUTDOORS. IS IT RAN ABOVE GROUND AND AT LEAST |
| | 3.5 INCHES ABOVE GROUND? FBC FG 404.9 |
| | |
| | 2) IS THE STEEL PIPING BURIED UNDERGROUND? IF SO, HOW |
| | IS IT PROTECTED? FBC FG 404.11. |
| | |
| | 3) IF PIPING IS BURIED PLEASE SHOW THE DEPTH OF THE |
| | UNDERGROUND PIPING. FBC FG 404.12 |
| | |
| | 4) PLEASE INDICATE DISTANCE OF GENERATOR EXHAUST FROM |
| | ANY OPERABLE OPENING INTO THE BUILDING. FBC RES |
| | R303.5.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |