| 2021-03-09 15:51:15 | PLAN REVIEW / FUEL GAS |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | NOTICE: PROVISO ON PLAN PAGE P2.1 SEPERATE FUEL GAS |
| | PERMIT REQUIRED FOR GENERATORS. |
| | |
| | |
| | 1. SUBMIT MANUFACTURERS SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| | 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | |
| | 2. SUBMIT GAS REGULATOR SPECIFICATIONS. 2017 FBC FUEL |
| | GAS SEC.305.1 OR 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | |
| | 3. REGULATORS SHALL HAVE A UNION INSTALLED WITHIN 1 |
| | FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2 |
| | |
| | 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| | FBC FG SECS. 402.2 AND 301.3 OR 2017 FBC RES. SEC. |
| | G2413.2 AND G2404.3. |
| | |
| | 5. CHANGE GOVERNING CODE ON GAS PLAN TO 2020 FBC FUEL |
| | GAS |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |