| Plan Review Notes For Permit 21010946 |
| Permit Number |
21010946 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-09 15:14:04 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: PROVISO ON PLAN PAGE S2 SEPERATE PERMIT | | | REQUIRED FOR SITE WALLS. | | | | | | 1. DEMO PLAN PAGE A-001 SHOWS FRONT DOOR TO BE REMOVED. | | | PROPOSED FLOOR PLAN S1.0 DOES NOT SHOW INSTALLATION OF | | | NEW DOOR. PLEASE CLARIFY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE DESIGN WIND PRESSURES FOR FRONT DOOR | | | OPENING. | | | R301.2.1 WIND DESIGN CRITERIA. | | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | | FROM FIGURE R301.2(4). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|