| 2021-05-12 21:50:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS |
| | |
| | |
| | |
| | 1. LOAD CALCULATION SHOWN DOES NOT APPEAR TO FOLLOW THE |
| | STANDARD OR OPTIONAL CALCULATION IN NEC 220.40 NEC |
| | 220.82 |
| | |
| | SMALL APPLIANCE CIRCUITS ARE TO BE MINIMUM 1500VA EACH |
| | IN LOAD CALC PER NEC 220.52 |
| | |
| | ALL FIXED APPLIANCES AND HEAT OR AC (WHICHEVER IS |
| | GREATER) ALSO NOT SHOWN. |
| | |
| | 4/0 AWG CU SHOWN FROM MAIN BREAKER PANEL TO MAIN LUG |
| | PANEL INSIDE. THIS IS NOT A CODE VIOLATION BUT #4 AWG |
| | COPPER SHOWN FOR SERVICE ENTRANCE CONDUCTORS. PERHAPS A |
| | TYPO?? |
| | |
| | 2. *** SATISFIED*** |
| | |
| | 3. SEVERAL CIRCUITS ARE STILL SHOWN WITHOUT AFCI |
| | PROTECTION REQUIRED PER NEC 210.12.. PLEASE PROVIDE |
| | CORRECTION. |
| | |
| | 4. SATISFIED |
| | |
| | 5. SATISFIED |
| | |
| | 6. SATISFIED |
| | |
| | 7. SATISFIED |
| | |
| | 8. SATISFIED |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |