| 2021-02-02 13:57:34 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21010935 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW CFM?S AT THE GRILLES TO THE BEDROOMS. |
| | FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THE RETURN AIR PATH FROM BEDROOMS TO THE |
| | AHU. FBC RES M1602.3 |
| | |
| | 3) PLEASE SHOW THE MINIMUM REQUIRED BATH EXHAUST FOR |
| | EACH BATHROOM. FBC RES TABLE M1507.4 |
| | |
| | 4) PLEASE SHOW THE REQUIRED KITCHEN EXHAUST. FBC RES |
| | TABLE M1507.4 |
| | |
| | 5) PLEASE SHOW THE REQUIRED MAKE UP AIR FOR THE DRYER. |
| | FBC M 504.6 |
| | |
| | 6) PLEASE EXPLAIN THE PURPOSE OF THE ERV IN THIS |
| | DESIGN. IT APPEARS THAT IN THE SOUTHERN FLORIDA CLIMATE |
| | THAT THIS SYSTEM WILL NOT WORK A LOT OF THE TIME OR |
| | THAT YOU WOULD BE DUMPING HOT HUMID OUTDOOR AIR INTO |
| | THE KITCHEN. THIS COULD MAKE THE AHU-1 WORK HARDER TO |
| | REMOVE THE HUMIDITY. |
| | |
| | 7) PLEASE PROVIDE DETAIL MOUNTING OF THE CONDENSING |
| | UNIT. FBC RES M1307.2 |
| | |
| | 8) PLEASE SHOW THE CONDENSATION ROUTING DETAILS ALONG |
| | WITH THE AUXILIARY AND SECONDARY DRAIN SYSTEMS. FBC RES |
| | M1411.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |