| 2021-02-10 12:45:02 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21010904 |
| | 2/10/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: THE SANITARY RISER SHOWS A NON-COMPLIANT |
| | BATHROOM WET VENT- SECTION P3108.2.1 FBC RES- NOT MORE |
| | THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE |
| | UPSTREAM OF THE DRY VENTED FIXTURE DRAIN CONNECTION. |
| | THE RISER SHOWS THE SHOWER AND THE WATER CLOSET BOTH |
| | DISCHARGING UPSTREAM. |
| | |
| | 2) P1: A CLEANOUT IS REQUIRED AT THE JUNCTION OF THE |
| | BATHROOM BUILDING DRAIN AND THE BUILDING SEWER- SECTION |
| | P3005.2.3 FBC P. |
| | |
| | 3) P1: THE PLUMBING FIXTURE NOTES- C, D, E INDICATE |
| | BOTH AN EXISTING TUB AND AN EXISTING SHOWER- PLEASE |
| | CLARIFY- SECTION 107.2.1 WPB. |
| | |
| | 4) P1: REMOVE ALL FIXTURES FROM THE SCHEDULE THAT ARE |
| | NOT BEING USED IN THE PROPOSED PROJECT- SECTION 107.2.1 |
| | WPB. |
| | |
| | 5) P1: IF APPLICABLE, SHOW THE WATER SUPPLY LINE TO THE |
| | REFRIGERATOR ICE MAKER INCLUDING THE REQUIRED BACKFLOW |
| | PREVENTER AND WATER HAMMER ARRESTOR- SECTIONS P2902.1 & |
| | P2903.5 FBC RES. |
| | |
| | 6) P1: PROVIDE A SHOWER PAN LINER DETAIL- SECTION |
| | P2709.1 & P2709.2 FBC RES. |
| | |
| | 7) P1: PLEASE NOTE THAT SEPARATE RESIDENCES ON THE SAME |
| | PROPERTY MAY REQUIRE INSTALLATION OF A BACKFLOW |
| | PREVENTER AT THE WATER METER. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |