2021-02-10 12:45:021ST REVIEW FBC-2020 RES.
 PERMIT- 21010904
 2/10/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SANITARY RISER SHOWS A NON-COMPLIANT
 BATHROOM WET VENT- SECTION P3108.2.1 FBC RES- NOT MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY VENTED FIXTURE DRAIN CONNECTION.
 THE RISER SHOWS THE SHOWER AND THE WATER CLOSET BOTH
 DISCHARGING UPSTREAM.
  
 2) P1: A CLEANOUT IS REQUIRED AT THE JUNCTION OF THE
 BATHROOM BUILDING DRAIN AND THE BUILDING SEWER- SECTION
 P3005.2.3 FBC P.
  
 3) P1: THE PLUMBING FIXTURE NOTES- C, D, E INDICATE
 BOTH AN EXISTING TUB AND AN EXISTING SHOWER- PLEASE
 CLARIFY- SECTION 107.2.1 WPB.
  
 4) P1: REMOVE ALL FIXTURES FROM THE SCHEDULE THAT ARE
 NOT BEING USED IN THE PROPOSED PROJECT- SECTION 107.2.1
 WPB.
  
 5) P1: IF APPLICABLE, SHOW THE WATER SUPPLY LINE TO THE
 REFRIGERATOR ICE MAKER INCLUDING THE REQUIRED BACKFLOW
 PREVENTER AND WATER HAMMER ARRESTOR- SECTIONS P2902.1 &
 P2903.5 FBC RES.
  
 6) P1: PROVIDE A SHOWER PAN LINER DETAIL- SECTION
 P2709.1 & P2709.2 FBC RES.
  
 7) P1: PLEASE NOTE THAT SEPARATE RESIDENCES ON THE SAME
 PROPERTY MAY REQUIRE INSTALLATION OF A BACKFLOW
 PREVENTER AT THE WATER METER. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  