Plan Review Notes For Permit 21010878
Permit Number 21010878
Review Stop P
Sequence Number 2
Notes
Date Text
2021-05-11 16:46:4021010878 8170 OKEECHOBEE BLVD # 4
  
  
 PLAN IS APPROVED WITH PROVISO: A REVISED PLUMBING PLAN
 SHALL BE SUBMITTED AS A REVISION AND SHALL BE APPROVED
 AND ON SITE PRIOR TO THE FIRST INSPECTION. REVISED
 PLANS SHALL REFLECT THE FOLLOWING AS REDLINED IN THE
 PERMIT PLAN SUBMITTED FOR THIS REVIEW.
  
 1.FULL OPEN VALVES SHALL BE REQUIRED AT TOP NOT THE
 BOTTOM OF NEW DOWN-FEED PIPES TO NEW SINK AND DRINKING
 FOUNTAIN AS REQUIRED BY FBC PL 606.1.5
  
 2.REFER TO EWC AND REC PUMP DETAIL THIS PAGE
  
 3.REDRAW RETURN AT POINT OF CONNECTION TO COLD WATER
  
 4.PROVIDE NOTE AT FIXTURE SCHEDULE "MIXING VALVE AT THE
 POINT OF DELIVERY AT THE LAVATORY AS REQUIRED BY FBC PL
 419.5."
  
 5.SEQUENCE OF SHUT OFF VALVE AND CHECK VALVE SHALL BE
 REVERSED FOR SERVICEABILITY WITH CHECK VALVE DOWNSTREAM
 OF SHUT OFF VALVE.
  
 6.PROVIDE A PIPE HANGER DETAIL WITH NOTE STATING "PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 CALL OR EMAIL WITH ANY QUESTION
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  