Plan Review Notes
Plan Review Notes For Permit 21010878
Permit Number 21010878
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-02 15:36:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21010878 8170 OKEECHOBEE BLVD # 4
 1ST REVIEW
 PLUMBING COMMENTS:
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, PROVIDE OCCUPANCY AND OCCUPANCY
 LOAD. BASED ON SAID OCCUPANCY AND OCCUPANCY LOAD,
 PROVIDE PLUMBING FIXTURE SCHEDULE SHOWING COMPLIANCE
 WITH FBC PL TABLE 403.1.
  
 2.REGARDING SCHEDULED TITAN N120 TANKLESS WATER HEATER
 NOTED ON SHEET 3.1, THE UNIT ELECTRICAL CHARACTERISTICS
 ARE 11.8KW/240V. THE ELECTRICAL SCHEDULE ON SHEET 4.1
 INDICATES 8KW. PER WPB FBC 107.2.1, CLARIFY AND/OR
 RECONCILE. ADDITIONALLY, PROVIDE AN EQUIPMENT SCHEDULE
 FOR THE WATER HEATER PROVIDING SIZE OF PLUMBING
 CONNECTIONS AND ELECTRICAL CHARACTERISTICS. PROVIDE
 MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL FOR
 THE SAME.
  
 3.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 SCHEDULE INDICATING PLUMBING FIXTURE TYPE WITH SIZED
 PLUMBING CONNECTIONS.
  
 4.REFER TO SHEET 1.1. SHOW CLEAR SPACE FOR SINK IN NEW
 CONSULT ROOM #3 SHOWING COMPLIANCE WITH SHOWING
 COMPLIANCE WITH FBC ACC SECTION 305.
  
 5.REFER TO SHEET 3.1, FIG. 27 DRINKING FOUNTAIN. PLEASE
 SEE BUILDING COMMENT. 1C)(1) SPOUT OUTLETS/ DRINKING
 FOUNTAINS. 2020 ACCESS. CODE. SPOUT OUTLETS SHALL
 COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
 PER WPB FBC REVISE DETAIL TO REFLECT THE REQUIREMENTS
 OR IF SHOWING COMPLIANCE ON SHEET 1.1 THEN REMOVE
 EXISTING DETAIL TO AVOID CONFUSION.
  
 6.REFER TO SHEET 3.1, WATER DISTRIBUTION; 1/2 INCH HOT
 AND COLD WATER IS NOTED AT THE DRINKING FOUNTAIN. PER
 WPB FBC 107.2.1, CLARIFY.
  
 7. REFER TO SHEET 3.1, WATER DISTRIBUTION; NEW HOT AND
 COLD WATER DISTRIBUTION IS SIZED 5/8 INCH. THERE IS NO
 5/8 INCH (THIS IS AN O.D. SIZE WHICH IS USED FOR
 REFRIGERANT PIPING) NOMINAL SIZE PIPE AVAILABLE FOR
 PLUMBING DESIGNATION. 1/2 INCH NOMINAL IS THE
 DESIGNATION THAT WOULD BE USED FOR 5/8 INCH O.D. IF
 THIS IS THE SIZE YOU INTENDED TO USE, PLEASE INDICATE
 IT ON THE PLANS TO AVOID CONFUSION AS REQUIRED BY WPB
 FBC 107.2.1.
  
 8.PER WPB FBC 107.2.1, PROVIDE FINISH WALL SCHEDULE FOR
 BATHROOM. REFER TO FBC PL 310.3 AND FBC 1210.2.2. WALLS
 AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT
 THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS
 THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE
 THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD
 BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 9.PLEASE REFER TO COMMENTS MADE BY BUILDING PLANS
 EXAMINER. 1B) BUILDING PROVISO: PLEASE NOTE IF IN THE
 FIELD THE GRAB BARS ARE EITHER TO HIGH OR TO LOW UNDER
 THE 2020 EXISTING BUILDING CODE, THE EXISTING BUILDING
 CODE REFERS BACK TO THE 2020 ACCESSIBILITY CODE AND THE
 20 % DISPROPORTION COST RULE. UP TO $5,900 DOLLARS IN
 VALUE ABOVE THE CONTRACT VALUE CAN BE REQUIRED FOR
 ACCESSIBILITY UPGRADES. 202.4.1. DISPROPORTIONATE COST.
 PLEASE NOTE, THIS COULD ALSO APPLY TO THE EXISTING
 LAVATORY AND WATER CLOSET IF THEY ARE NOT COMPLIANT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 21010878 8170 OKEECHOBEE BLVD # 4