| 2021-01-27 11:19:47 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | 1) SHEET A 201 - THERE ARE NO INDICATION OF SMOKE |
| | ALARMS OUTSIDE THE NEW CORRIDOR SPACE BY THE 2ND |
| | BATHROOM. |
| | |
| | PER NFPA 101, CH 31. EXISTING APARTMENT BUILDINGS |
| | |
| | 31.3.4.5 SMOKE ALARMS. |
| | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, |
| | SMOKE ALARMS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS |
| | MODIFIED BY 31.3.4.5.2, |
| | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS |
| | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING |
| | BASEMENTS. |
| | |
| | PLEASE REVIEW AND ENSURE THERE IS A SA IN THIS |
| | LOCATION. |
| | |
| | |
| | 2) SHEET A 201 - THE ENTRY DOOR TO THE SPARE BEDROOM |
| | WAS MOVED. THERE ARE NO INDICATIONS OF A SMOKE ALARM |
| | WITHIN THIS ROOM AND ANY PREVIOUS LOCATION MAY HAV |
| | EBEEN AFEECTED BY THE DOOR LOCATION CHANGE.. |
| | |
| | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR |
| | A COMPLETE, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 31.3.5, |
| | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA |
| | IN |
| | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. |
| | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE |
| | PERMITTED TO BE |
| | BATTERY POWERED. |
| | |
| | PLEASE REVIEW AND ENSURE THERE IS A SA IN THIS |
| | LOCATION. |
| | |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |