2021-02-09 12:16:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010826
 2/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2: REVIEW FIXTURE SCHEDULE NOTE A ON P2
 AND SHOW THE TMV FOR THE LAVATORY IN THE RISER DRAWING
 ON P1- SECTIONS 419.5 AND 607.1.2 FBC P.
  
 2) P2- INSTA-HOT PIPING DETAIL: A) A DEDICATED FULL
 OPEN SHUT OFF VALVE IS REQUIRED FOR THE WATER HEATER-
 SECTIONS 503.1 & 606.1(8) FBC P. B) SHOW THE TMV VALVE
 LOCATION AND PIPE CONNECTIONS- SECTION 607.1.2 FBC P.
  
 3) P1: SHOW WATER HAMMER ARRESTORS AND BACKFLOW
 PREVENTERS FOR THE WATER SUPPLY PIPES TO THE
 REFRIGERATION AND DISHWASHER- SECTIONS 604.9 & 608.3
 FBC P. BACKFLOW PREVENTION TO THE DISHWASHER CAN BE
 PROVIDED BY AN AIR GAP- SECTION 409.2.
  
 4) A1.1: PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE DIAGRAMS AT THE FIXTURES- SECTIONS 604.3 & 606.2
 FBC ACC.
  
 5) CLARIFY IF THE EXISTING SLAB WILL BE X-RAYED IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  