| 2021-02-09 12:16:20 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21010826 |
| | 2/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P1 & P2: REVIEW FIXTURE SCHEDULE NOTE A ON P2 |
| | AND SHOW THE TMV FOR THE LAVATORY IN THE RISER DRAWING |
| | ON P1- SECTIONS 419.5 AND 607.1.2 FBC P. |
| | |
| | 2) P2- INSTA-HOT PIPING DETAIL: A) A DEDICATED FULL |
| | OPEN SHUT OFF VALVE IS REQUIRED FOR THE WATER HEATER- |
| | SECTIONS 503.1 & 606.1(8) FBC P. B) SHOW THE TMV VALVE |
| | LOCATION AND PIPE CONNECTIONS- SECTION 607.1.2 FBC P. |
| | |
| | 3) P1: SHOW WATER HAMMER ARRESTORS AND BACKFLOW |
| | PREVENTERS FOR THE WATER SUPPLY PIPES TO THE |
| | REFRIGERATION AND DISHWASHER- SECTIONS 604.9 & 608.3 |
| | FBC P. BACKFLOW PREVENTION TO THE DISHWASHER CAN BE |
| | PROVIDED BY AN AIR GAP- SECTION 409.2. |
| | |
| | 4) A1.1: PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR |
| | SPACE DIAGRAMS AT THE FIXTURES- SECTIONS 604.3 & 606.2 |
| | FBC ACC. |
| | |
| | 5) CLARIFY IF THE EXISTING SLAB WILL BE X-RAYED IN |
| | ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED |
| | FLOOR TENDONS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |