| 2021-03-01 09:45:58 | 2ND REVIEW FBC-2020 RES. |
| | PERMIT- 21010824 |
| | 3/1/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED STILL EXIST. NOTES |
| | HAVE BEEN ADDED IN CAP LETTERS. |
| | |
| | 1) THE KITCHEN PLUMBING RISER IS NOT DRAWN IN |
| | COMPLIANCE WITH THE CODE. RELOCATE THE WASHING MACHINE |
| | TO THE LEFT SIDE OF THE RISER AND REMOVE THE CONNECTION |
| | TO THE COMMON VENT SERVING THE KITCHEN SINK DRAINS. |
| | PROVIDE A 2 IN. STANDPIPE AND TRAP AND SHOW THE |
| | STANDPIPE CONNECTING TO EITHER A 3 IN. HORIZONTAL OR |
| | VERTICAL DRAIN- SECTIONS P3107.1 & P3201.7 FBC RES, AND |
| | SECTION 406.2 FBC FG. CONNECTION TO A VERTICAL STACK |
| | WILL REQUIRE A STACK VENT SIZED IN ACCORDANCE WITH |
| | SECTION P3109.3. THE NEW RISER SHOWS A 1-1/2 STANDPIPE |
| | AND A 2 IN. HORIZONTAL BRANCH DRAIN. THE SINKS NEED A |
| | COMMON VENT- SECTION P3701.1 FBC RES. |
| | |
| | 4) PROVIDE THE DIMENSIONS OF THE MASTER BATH SHOWER AND |
| | THE WIDTH OF THE SHOWER DOOR- SECTION P2708.1 & |
| | P2708.1.1 FBC RES. THE REVISED PLAN SHOWS AN UNDERSIZED |
| | SHOWER DOOR WIDTH OF 18-7/8 IN. REFER TO SECTION |
| | P2708.1.1 FBC RES.- MINIMUM 22 IN. UNOBSTRUCTED WIDTH |
| | REQUIRED. |
| | |
| | 7) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |