| 2021-03-01 10:21:42 | 2ND REVIEW FBC-2020 RES. |
| | PERMIT- 21010824 |
| | 2/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED STILL EXIST. NOTES |
| | HAVE BEEN ADDED IN CAP LETTERS. |
| | |
| | 1) PROVIDE A GAS PIPING RISER DRAWING FOR INSTALLATION |
| | OF THE NEW GAS WATER HEATER AND ALL PROPOSED GAS-FIRED |
| | APPLIANCES AND EQUIPMENT- SECTION 107.3.5.3 WPB. NOT |
| | PROVIDED. |
| | |
| | GAS RISER- PROVIDE THE FOLLOWING- FBC-2020 RES. FUEL |
| | GAS. |
| | A) TOTAL LOAD OF THE SYSTEM AND INDIVIDUAL APPLIANCE |
| | LOADS. |
| | B) TOTAL DEVELOPED LENGTH OF THE SYSTEM AND INDIVIDUAL |
| | BRANCH LENGTH MEASURMENTS. |
| | C) TYPES AND SIZES OF PIPING AND RISERS. |
| | D) DELIVERY PRESSURE AT THE METER AND THE SYSTEM. |
| | E) LOCATIONS OF SHUTOFF VALVES AND REGULATORS. |
| | F) PIPE SIZING TABLES USED |
| | |
| | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE |
| | NEW WATER HEATER AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS IN ACCORDANCE WITH SECTION G2448.1 FBC |
| | RES, AND TABLE C404.2 FBC EC. PLEASE NOTE THE PLAN |
| | SYMBOL IS INDICATING A STORAGE TANK TYPE WATER HEATER |
| | AT THE EXTERIOR OF THE BUILDING WHICH APPEARS TO BE A |
| | PLAN ERROR. TANKLESS WATER HEATERS RATED FOR EXTERIOR |
| | INSTALLATION ARE TYPICALLY INSTALLED INSTEAD OF TANK |
| | HEATERS WHICH WILL REQUIRE PROTECTION FROM WIND AND |
| | WATER INTRUSION. EQUIPMENT SCHEDULE AND SPECS NOT FOR |
| | THE WH PROVIDED. THE SCHEDULE AND SPECS MAY BE DEFERRED |
| | SUBMITTALS HOWEVER THE PLAN SHOWS AN INCORRECT GAS LOAD |
| | OF 19,000 BTU- PLEASE CORRECT. |
| | |
| | 3) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1 |
| | WPB. NOT PROVIDED. THE APPLICATION MAY BE DEFFERRED AND |
| | SUBMITTED AT A LATER DATE AFTER MASTER PERMIT ISSUANCE- |
| | SECTION 105.1 WPB. |
| | |
| | 4) NEW SUBMITTED PLUMBING LAYOUT PLAN- SEE COMMENT #1 |
| | AND #2 ABOVE AND CORRECT THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |