| 2021-02-05 09:28:06 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21010809 |
| | 2/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET ALS1.0: THE PLUMBING FIXTURE CALCULATIONS ARE |
| | NOT IN COMPLIANCE WITH TABLE 403.3 FBC P. AN OCCUPANT |
| | LOAD OF 205 REQUIRES 4 MALE AND 4 FEMALE WATER CLOSETS, |
| | AND 3 MALE AND 3 FEMALE LAVATORIES. PLEASE CORRECT THE |
| | SCHEDULE AND THE PLANS. |
| | |
| | 2) THE NEW SINGLE USER TOILET ROOMS SHOWN IN THE |
| | ARCHITECTURAL AND PLUMBING PLANS ARE NOT IDENTIFIED AS |
| | EITHER MALE, FEMALE, OR UNISEX, AND NO SIGNAGE DETAILS |
| | HAVE BEEN PROVIDED- SECTIONS 403.2 & 403.4 FBC P. |
| | |
| | 3) SHEETS A2.1.3 & A2.1.4 SHOWING AREAS C & D DO NOT |
| | MATCH THE DEMO AND NEW WORK PLUMBING PLANS DESIGNATED |
| | FOR AREAS C & D. PLEASE CORRECT- SECTION 107.2.1 WPB. |
| | |
| | 4) SHEETS A2.1.3 & P.1.1.4: SHOW THE CLEAR FLOOR SPACE |
| | DIAGRAM AND DIMENSIONS FOR THE NEW STERILIZER SINK- |
| | SECTIONS 212.3 & 696.2 FBC ACC. |
| | |
| | 5) SHEET A4.02: PROVIDE AN ELEVATION DETAIL SHOWING THE |
| | KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION- |
| | 606.2 FBC ACC. |
| | |
| | 6) SHEETS P0.01, P1.1.2, P1.1.3, AND P1.1.4: SECTION |
| | 419.5 FBC- 2020 PLUMBING WAS CHANGED TO ALLOW |
| | LAVATORIES TO BE SUPPLIED WITH EITHER COLD OR TEMPERED |
| | WATER. THE FIXTURE SCHEDULE INDICATES HOT AND COLD |
| | WATER AND TEMPERATURE MIXER FAUCET, HOWEVER THE PLANS |
| | APPEAR TO SHOW COLD WATER SUPPLY ONLY TO THE |
| | LAVATORIES. PLEASE CLARIFY THE DESIGN INTENTION. |
| | |
| | 7) SHEET P1.1.5: PROVIDE VACUUM AND COMPRESSED AIR |
| | PIPING DIAGRAMS SHOWING POINTS OF CONNECTIONS AND NEW |
| | PIPING RUNS. PLEASE INCLUDE THE TYPES AND SIZES OF |
| | PIPING IN THE DRAWING. PROVIDE AN EQUIPMENT SCHEDULE |
| | FOR THE NEW OUTLET ENCLOSURE INDICATING MAKE, MODEL, |
| | AND LISTING, AND SUBMIT MANUFACTURER?S SPECIFICATIONS |
| | FOR THE ENCLOSURE AND THE PIPING- SECTION 107.2.1 WPB. |
| | PLEASE CLARIFY IF MEDICAL GAS ALTERATIONS ARE PROPOSED |
| | AND PROVIDE DETAILS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |