2021-07-16 15:01:384TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21010779
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE COMMENT 4 OF REVIEW CYCLE 3 BELOW:
 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE I.E. DINING ROOM, KITCHEN AND OFFICE BASED ON
 FBC M 403.3.1.1 AND TABLE 403.3.1.1 OR ASHRAE 62.1-
 2016
  
 2) IF ASHRAE 62.1-2016 IS USED PLEASE SUBMIT ENTIRE
 PROJECT BASED ON ASHRAE 62.1-2016 AS ALTERNATE MEANS
 AND METHODS. FBC M 104.11
  
 3) PLEASE HELP THIS REVIEWER UNDERSTAND THE ?SERVING
 AREA? LISTED IN THE OUTDOOR AIR CALCULATIONS, IS THIS
 NOT THE EXISTING DINING ROOM? BASED ON FBC M 403.3.1.1
 AND TABLE 403.3.1.1 THE DINING ROOM OCCUPANCY IS 61
 PEOPLE WITH 612 CFM OF REQUIRED OUTDOOR AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  