| Date |
Text |
| 2021-07-16 15:01:38 | 4TH REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21010779 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SEE COMMENT 4 OF REVIEW CYCLE 3 BELOW: |
| | 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| | OF SPACE I.E. DINING ROOM, KITCHEN AND OFFICE BASED ON |
| | FBC M 403.3.1.1 AND TABLE 403.3.1.1 OR ASHRAE 62.1- |
| | 2016 |
| | |
| | 2) IF ASHRAE 62.1-2016 IS USED PLEASE SUBMIT ENTIRE |
| | PROJECT BASED ON ASHRAE 62.1-2016 AS ALTERNATE MEANS |
| | AND METHODS. FBC M 104.11 |
| | |
| | 3) PLEASE HELP THIS REVIEWER UNDERSTAND THE ?SERVING |
| | AREA? LISTED IN THE OUTDOOR AIR CALCULATIONS, IS THIS |
| | NOT THE EXISTING DINING ROOM? BASED ON FBC M 403.3.1.1 |
| | AND TABLE 403.3.1.1 THE DINING ROOM OCCUPANCY IS 61 |
| | PEOPLE WITH 612 CFM OF REQUIRED OUTDOOR AIR. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |