2021-04-08 14:48:341ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010779
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MUA UNIT MUST MEET FBC M 508.1.1 MAKEUP AIR
 TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 2) THE APPLICATION INDICATES THIS IS FOR THE
 INSTALLATION OF THE KITCHEN HOODS AND GREASE DUCT AND
 MAKE UP AIR FOR THE HOODS. PLEASE REMOVE ALL UNRELATED
 DRAWINGS FROM THIS HOOD APPLICATION. THE HOOD, GREASE
 DUCT AND MAKE UP AIR IS A STAND ALONE PERMIT THAT
 SHOULD BE SEPARATELY FROM THE MAIN PERMIT. FBC 107.2.1
  
 3) SHEET H-1 INDICATES THE TYPE II HOOD IS TO BE
 DISABLED ALTHOUGH IT APPEARS THERE WILL BE SOME TYPE OF
 COOKING UNDER THIS HOOD. PLEASE EXPLAIN WHY THERE IS NO
 NEED FOR A HOOD. FBC 507.1
  
 THE AIR BALANCE REPOT MUST MEET: FBC M 508.1.2AIR
 BALANCE.
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION. (THE BATH ROOM EXHAUST MUST
 BE INCLUDED IN THE AIR BALANCE REPORT).
  
 4) WHAT IS THE TYPE OF CONSTRUCTION FOR THIS BUILDING?
  
 PLEASE SHOW THE GREASE DUCT WILL HAVE THE REQUIRED
 CLEARANCE TO COMBUSTIBLES: FBC M 510.9.2CLEARANCE TO
 COMBUSTIBLES.
 DUCTS SHALL HAVE A CLEARANCE TO COMBUSTIBLES IN
 ACCORDANCE WITH TABLE 510.9.2. EXHAUST GASES HAVING
 TEMPERATURES IN EXCESS OF 600?F (316?C) SHALL BE
 EXHAUSTED TO A CHIMNEY IN ACCORDANCE WITH SECTION
 511.2.
  
 5) PLEASE SHOW THE DISTANCE FROM UNITS TO ROOF EDGE.
 FBC M 304.11
  
 6) PLEASE SHOW ACCESS TO THE UNITS ON THE ROOF. FBC M
 306.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  