| 2021-04-08 14:48:34 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21010779 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) MUA UNIT MUST MEET FBC M 508.1.1 MAKEUP AIR |
| | TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| | HVAC SYSTEM. |
| | |
| | |
| | 2) THE APPLICATION INDICATES THIS IS FOR THE |
| | INSTALLATION OF THE KITCHEN HOODS AND GREASE DUCT AND |
| | MAKE UP AIR FOR THE HOODS. PLEASE REMOVE ALL UNRELATED |
| | DRAWINGS FROM THIS HOOD APPLICATION. THE HOOD, GREASE |
| | DUCT AND MAKE UP AIR IS A STAND ALONE PERMIT THAT |
| | SHOULD BE SEPARATELY FROM THE MAIN PERMIT. FBC 107.2.1 |
| | |
| | 3) SHEET H-1 INDICATES THE TYPE II HOOD IS TO BE |
| | DISABLED ALTHOUGH IT APPEARS THERE WILL BE SOME TYPE OF |
| | COOKING UNDER THIS HOOD. PLEASE EXPLAIN WHY THERE IS NO |
| | NEED FOR A HOOD. FBC 507.1 |
| | |
| | THE AIR BALANCE REPOT MUST MEET: FBC M 508.1.2AIR |
| | BALANCE. |
| | DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN |
| | VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM |
| | INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN |
| | OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND |
| | REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET |
| | EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR |
| | AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE |
| | PLUS THE NET EXFILTRATION. (THE BATH ROOM EXHAUST MUST |
| | BE INCLUDED IN THE AIR BALANCE REPORT). |
| | |
| | 4) WHAT IS THE TYPE OF CONSTRUCTION FOR THIS BUILDING? |
| | |
| | PLEASE SHOW THE GREASE DUCT WILL HAVE THE REQUIRED |
| | CLEARANCE TO COMBUSTIBLES: FBC M 510.9.2CLEARANCE TO |
| | COMBUSTIBLES. |
| | DUCTS SHALL HAVE A CLEARANCE TO COMBUSTIBLES IN |
| | ACCORDANCE WITH TABLE 510.9.2. EXHAUST GASES HAVING |
| | TEMPERATURES IN EXCESS OF 600?F (316?C) SHALL BE |
| | EXHAUSTED TO A CHIMNEY IN ACCORDANCE WITH SECTION |
| | 511.2. |
| | |
| | 5) PLEASE SHOW THE DISTANCE FROM UNITS TO ROOF EDGE. |
| | FBC M 304.11 |
| | |
| | 6) PLEASE SHOW ACCESS TO THE UNITS ON THE ROOF. FBC M |
| | 306.5 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |