| Date |
Text |
| 2021-01-27 10:52:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET HOOD 1 - THERE ARE NO INDICATIONS OF FLOOR |
| | PLAN SHOWING THE EXACT LOCATION WITHIN THE BUILDING |
| | SPACE, INCLUDING DIMENSIONS. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH NFPA 96 |
| | |
| | |
| | |
| | |
| | 2) SHEET KEF - THERE ARE NO INDICATIONS OF THE EXACT |
| | LOCATION ON THE ROOF, INCLUDING DIMENSIONS TO OTHER |
| | EQUIPMENT INCLUDING A/C AND AND OTHER VENTS. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLAINCE WITH NFPA 96 |
| | |
| | |
| | |
| | |
| | 3) SHEET MUA 1 - THERE ARE NO INDICATIONS OF THE |
| | CLEARENCES OR SUPPORTS GOING UP THROUGH THE TRUSS |
| | SYSTEM TO THE ROOF, INCLUDING DIMENSIONS. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLAINCE WITH NFPA 96 |
| | |
| | |
| | |
| | |
| | 4) SHEET FIRE SYSTEM 1 - THERE ARE INDICATIONS OF A |
| | FIRE SUPPRESSION SYSTEM. |
| | |
| | THE FIRE SUPPRSSION SYSTEM SHALL BE SUBMITTED THROUGH |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | THE FIRE SUPPRESSION SYSTEM IS NOT APPROVED WITH THIS |
| | PERMIT AND SHALL NOT BE INSTALLED UNDER THIS PERMIT. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |