Plan Review Notes
Plan Review Notes For Permit 21010770
Permit Number 21010770
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-28 12:55:35WINDOWS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WINDOW PRODUCT APPROVAL PROVIDED REQUIRES SHUTTERS -
 PLEASE PROVIDE THE SHUTTER PRODUCT APPROVAL OR PROVIDE
 THE EXISTING SHUTTER PERMIT NUMBER.
 2) TO BE EXEMPT FROM THE REQUIRED SHUTTERS - SHOW THE
 GLAZED AREA PER FBC EXISTING BUILDING 707.4REPLACEMENT
 OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16
 OF THE FLORIDA BUILDING CODE, BUILDING.
 EXCEPTIONS:
 1.OPENING PROTECTION EXCEPTION: FOR ONE- AND TWOFAMILY
 DWELLINGS CONSTRUCTED UNDER CODES OTHER THAN THE
 FLORIDA BUILDING CODE AND LOCATED IN WINDBORNE DEBRIS
 REGIONS, THE REPLACEMENT OF GARAGE DOORS AND EXTERIOR
 DOORS WITH GLAZING, SLIDING GLASS DOORS, GLASS PATIO
 DOORS, SKYLIGHTS, AND OPERABLE AND INOPERABLE WINDOWS
 WITHIN ANY 12-MONTH PERIOD SHALL NOT BE REQUIRED TO
 HAVE OPENING PROTECTION BUT SHALL BE DESIGNED FOR WIND
 PRESSURES FOR ENCLOSED BUILDINGS, PROVIDED THE
 AGGREGATE AREA OF THE GLAZING IN THE REPLACED
 COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE AGGREGATE
 AREA OF THE GLAZED OPENINGS IN THE DWELLING OR DWELLING
 UNIT.